Three-Phase 200 V / 400 V Class (2A0343, 2A0396, and 4A0361 to 4A0590)
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
–
3
+
1
+
CIMR-ZШ2A0343 and 2A0396
CIMR-ZШ4A0414 to 4A0590
L3
L2
L1
L3
L3 L2
L2 L1
L1
L3 L2 L1
E
PE
B
C
D
E
D
F
H
G
A
K
I
J
A – Ground the cable shield
B – Enclosure panel
C – Metal plate
D – Grounding surface (remove any
paint or sealant)
E – Drive
F – Motor cable (braided shield cable,
max. 10 m)
G – Motor
H – Cable Clamp
I – Ground plate (scrape off any
visible paint)
J – EMC noise filter
K – Make sure the ground wire is
grounded
Figure D.5 EMC Filter and Drive Installation for CE Compliance (2A0343, 2A0396, and 4A0361 to 4A0590)