H5-08 = 0, MEMOBUS/Modbus; default: 3
H5-08 = 1, N2 (Metasys); default: 3
H5-08 = 2, P1 (APOGEE FLN); default: 2
H5-08 = 3, BACnet; default: 3

H5-02

Communication Speed

H5-02

Communication Speed

0

<1>

1200 bps

5

<1>

38400 bps

1

<1>

2400 bps

6

<1>

57600 bps

2

4800 bps

7

<1>

76800 bps

3

<1>

9600 bps

8

<1> <2>

115200 bps

4

<1>

19200 bps

<1> Not available when H5-08 is set to 2 P1 (APOGEE FLN).
<2> Not available when H5-08 is set to 0 (MEMOBUS/Modbus) or 1 (Metasys N2).

n

H5-03: Communication Parity Selection

Sets the parity used for communications.

Note:

Cycle the power after changing this parameter to enable the new setting.

No.

Name

Setting Range

Default

H5-03

Communication Parity Selection

0 to 2

0

Setting 0: No parity
Setting 1: Even parity
Setting 2: Odd parity

n

H5-04: Stopping Method after Communication Error

Selects the stopping method after a communications error (CE) has occurred.

No.

Name

Setting Range

Default

H5-04

Stopping Method after CE

0 to 4

3

Setting 0: Ramp to Stop

Uses the deceleration time currently enabled.

Setting 1: Coast to Stop
Setting 2: Fast Stop
Setting 3: Alarm Only - Operation Continues
Setting 4: Run at d1-04

n

H5-05: Communication Fault Detection Selection

Enables or disables the CE detection for communications.

No.

Name

Setting Range

Default

H5-05

Communication Fault Detection Selection

0 or 1

1

Setting 0: Disabled

No communication error detection. The drive continues operation.

Setting 1: Enabled

If the drive does not receive data from the master for longer than the time set to H5-09, then a CE fault will be triggered and

the drive will operate as determined by parameter H5-04.

n

H5-06: Drive Transmit Wait Time

Sets the time the drive waits after receiving data from a master until responding data.

No.

Name

Setting Range

Default

H5-06

Drive Transmit Wait Time

5 to 65 ms

5 ms

4.13 Advanced Drive Setup Adjustments

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual