Yaskawa AC Drive Z1000 User Manual

Page 270

Advertising
background image

u

Three-Phase 400 V Class Drive Models 4A0124 to 4A0302

Table A.5 Power Ratings Continued (Three-Phase 400 V Class)

Item

Specification

CIMR-Zo4A

0124

0156

0180

0240

0302

Maximum

Applicable

Motor

Capacity

Input Voltage

460 V or higher

<1>

HP

100

125

150

200

250

kW

75

90

110

150

185

Input Voltage

lower than 460 V

<2>

HP

75

100

125

150

220

kW

55

75

90

110

160

Input

Input Current (A)

<3>

124

156

180

240

302

Rated Voltage

Rated Frequency

Three-phase 380 to 480 Vac 50/60 Hz / 510 to 680 Vdc

Allowable Voltage Fluctuation

-15 to 10%

Allowable Frequency Fluctuation

±5%

Minimum Power Supply Capacity (kVA)

104

130

150

200

252

Output

Rated Output Capacity

(kVA)

Input Voltage

460 V or higher

<4>

99

124

143

191

241

Input Voltage

lower than 460 V

<5>

86

108

125

166

209

Rated Output Current (A)

124

<6>

156

<6>

180

<6>

240

<7>

302

<7>

Overload Tolerance

110% of rated output current for 60 s

140% of rated output current for 0.5 s

Carrier Frequency

User adjustable between 1 and 10 kHz

(Maximum Frequency varies with Rated Output Capacity)

Maximum Output Voltage (V)

Three-phase 380 to 480 V (proportional to input voltage)

Maximum Output Frequency (Hz)

240 Hz

Harmonics

Reduction

DC Link Choke

Built-in

EMC

Filter (IEC/EN 61800-3 Category 2)

Built-in

<1> The motor capacity (HP) refers to an NEC Table 430.250 208 V motor. The rated output current of the drive output amps should be equal to or

greater than the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.

<2> The motor capacity (HP) refers to a Yaskawa 4-pole motor. The rated output current of the drive output amps should be equal to or greater than the

motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.

<3> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring

connections, and power supply impedance.

<4> Rated motor capacity is calculated with a rated output voltage of 460 V.
<5> Rated motor capacity is calculated with a rated output voltage of 400 V.
<6> Carrier frequency is set to 5 kHz. Current derating is required to raise the carrier frequency.
<7> Carrier frequency is set to 4 kHz. Current derating is required to raise the carrier frequency.

A.1 Power Ratings

270

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual