Yaskawa AC Drive Z1000 User Manual

Page 167

Advertising
background image

No.

Name

Setting Range

Default

b5-40

Frequency Reference Monitor Content During PI

0, 1

0

Setting 0: Frequency Reference after PI

Monitor U1-01 displays the frequency reference increased or reduced for the PI output.

Setting 1: Frequency Reference

Monitor U1-01 displays the frequency reference value.

n

b5-41: PI Unit Selection

Sets the display units in U5-14 and U5-15.

No.

Name

Setting Range

Default

b5-41

PI Unit Selection

0 to 14

0

Setting 0: WC (Inch of Water)
Setting 1: PSI (Pounds per Square Inch)
Setting 2: GPM (Gallons per Minute)
Setting 3: F (Degrees Fahrenheit)
Setting 4: CFM (Cubic Feet per Minute)
Setting 5: CMH (Cubic Meters per Hour)
Setting 6: LPH (Liters per Hour)
Setting 7: LPS (Liters per Second)
Setting 8: Bar (Bar)
Setting 9: Pa (Pascal)
Setting 10: C (Degrees Celsius)
Setting 11: Mtr (Meters)
Setting 12: Ft (Feet)
Setting 13: LPM (Liters per Minute)
Setting 14: CMM (Cubic Meters per Minute)

n

b5-42: PI Output Monitor Calculation Method

No.

Name

Setting Range

Default

b5-42

PI Output Monitor Calculation Method

0 to 3

0

Setting 0: Linear

The monitor displays PI output.

Setting 1: Square Root

The monitor displays square root PI output.

Setting 2: Quadratic

The monitor displays 1/(PI output)

2

Setting 3: Cubic

The monitor displays 1/(PI output)

3

n

b5-43/b5-44: Custom PI Output Monitor Setting 1/2

Set the maximum monitor value at maximum frequency. U5-14 and U5-15 show Custom PI output. U5-14 shows the upper

4 digits and U5-15 shows the lower 4 digits. It shows 999999.99 maximum.

No.

Name

Setting Range

Default

b5-43

Custom PI Output Monitor Setting 2

0 to 9999

0

b5-44

Custom PI Output Monitor Setting 2

0.00 to 99.99

0.00

4.13 Advanced Drive Setup Adjustments

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual

167

4

Start-Up Programming & Operation