5.5 Alarm Detection

u

Alarm Codes, Causes, and Possible Solutions

Alarms are drive protection functions that do not necessarily cause the drive to stop. Once the cause of an alarm is removed,

the drive will return to the same status is was before the alarm occurred.
When an alarm has been triggered, the ALM light on the HOA keypad display blinks and the alarm code display flashes. If a

multi-function output is set for an alarm (H2-oo = 10), that output terminal will be triggered.

Note:

If a multi-function output is set to close when an alarm occurs (H2-oo = 10), it will also close when maintenance periods are reached,

triggering alarms LT-1 through LT-4 (triggered only if H2-oo = 2F).

Table 5.11 Alarm Codes, Causes, and Possible Solutions

HOA Keypad Display

Minor Fault Name

bb

Baseblock
Drive output interrupted as indicated by an external baseblock signal.

Cause

Possible Solutions

External baseblock signal was entered via one of

the multi-function input terminals (S1 to S7)

Check external sequence and baseblock signal input timing.

HOA Keypad Display

Minor Fault Name

bUS

Option Communication Error
• The connection was lost after initial communication was established.
• Assign a Run command frequency reference to the option.

Cause

Possible Solutions

Connection is broken or master controller stopped

communicating

• Check for faulty wiring.
• Correct the wiring.
• Check for disconnected cables and short circuits. Repair as needed.

Option is damaged

If there are no problems with the wiring and the fault continues to occur, replace the option.

The option is not properly connected to the drive

• The connector pins on the option are not properly lined up with the connector pins on the drive.
• Reinstall the option.

A data error occurred due to noise

• Check options available to minimize the effects of noise.
• Take steps to counteract noise in the control circuit wiring, main circuit lines and ground wiring.
• Try to reduce noise on the controller side.
• Use surge absorbers on magnetic contactors or other equipment causing the disturbance.
• Use recommended cables or some other type of shielded line. Ground the shield to the controller

side or on the input power side.

• Separate the wiring for communication devices from the drive input power lines.

HOA Keypad Display

Minor Fault Name

CALL

Serial Communication Transmission Error
Communication has not yet been established.

Cause

Possible Solutions

Communications wiring is faulty, there is a short

circuit, or something is not connected properly

• Check for wiring errors.
• Correct the wiring.
• Check for disconnected cables and short circuits. Repair as needed.

Programming error on the master side

Check communications at start-up and correct programming errors.

Communications circuitry is damaged

• Perform a self-diagnostics check.
• If the problem continues, replace either the control board or the entire drive. For instructions on

replacing the control board, contact Yaskawa or your nearest sales representative.

Termination resistor setting is incorrect

Install a termination resistor at both ends of a communication line. Set the internal termination resistor

switch correctly on slave drives. Place DIP switch S2 to the ON position.

HOA Keypad Display

Minor Fault Name

CE

MEMOBUS/Modbus Communication Error
Control data was not received correctly for two seconds.

Cause

Possible Solutions

5.5 Alarm Detection

218

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual