Drive output is shut off

Run

command

Output

frequency

Motor speed

ON

OFF

Figure 4.14 Coast to Stop

Note:

After a stop is initiated, any subsequent Run command entered will be ignored until the minimum baseblock time (L2-03) has expired. Do

not enter Run command until it has come to a complete stop. Use DC Injection at Start (

Refer to b2: DC Injection Braking and Short

Circuit Braking on page 282

) or Speed Search (

Refer to b3: Speed Search on page 283

) to restart the motor before it has completely

stopped.

Setting 2: DC Injection Braking to Stop

When the Run command is removed, the drive will enter baseblock (turn off its output) for the minimum baseblock time

(L2-03). When the minimum baseblock time has expired, the drive will inject the amount DC current set in parameter b2-02

into the motor windings to brake the motor. The stopping time in DC Injection Braking to Stop is significantly faster compared

to Coast to Stop.

Note:

This function is not available in OLV/PM control mode (A1-02 = 5).

Motor coasts

DC Injection Braking

with the current set in

b2-02

Run

command

Output

frequency

ON

OFF

Motor speed

Minimum Baseblock

Time (L2-03)

Figure 4.15 DC Injection Braking to Stop

DC Injection Braking time is determined by the value set to b2-04 and the output frequency at the time the Run command is

removed. It can be calculated by:

DC Injection brake time

(b2-04) x 10 x Output frequency

Max. output frequency (E1-04)

=

4.7 Basic Drive Setup Adjustments

130

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual