Refer to, For details on using this function, D2-03: master speed reference lower limit – Yaskawa AC Drive Z1000 User Manual

Page 170

Advertising
background image

No.

Parameter Name

Setting Range

Default

d1-01 to d1-04

Frequency Reference 1 to 4

0.00 to 240.00 Hz

<1>

<2>

0.00 Hz

<2>

d1-16

Frequency Reference 16

0.00 to 240.00 Hz

<1>

<2>

0.00 Hz

<2>

d1-17

Jog Frequency Reference

0.00 to 240.00 Hz

<1>

<2>

6.00 Hz

<2>

<1> The upper limit is determined by the maximum output frequency (E1-04) and upper limit for the frequency reference (d2-01).
<2> Setting units are determined by parameter o1-03. The default is “Hz” (o1-03 = 0).

Multi-Step Speed Selection

To use several speed references for a multi-step speed sequence, set the H1-oo parameters to 3 and 4. To assign the Jog

reference to a digital input, set H1-oo to 6.
Notes on using analog inputs as Multi-Speed 1 and 2:
• The first frequency reference (Multi-Speed 1) comes from the source specified in b1-01. When using an analog input terminal

to supply the frequency reference, assign the frequency reference source to the control terminals (b1-01 = 1).

• When an analog input is set to “Auxiliary frequency 1” (H3-02 or H2-06 = 2), the value set to this input will be used as the

Multi-Step Speed 2 instead of the value set to parameter d1-02. If no analog inputs are set for “Auxiliary frequency 1”, then

d1-02 becomes the reference for Multi-Step Speed 2.

Select the different speed references as shown in

Table 4.24

.

Figure 4.32

illustrates the multi-step speed selection.

Table 4.24 Multi-Step Speed Reference and Terminal Switch Combinations

Reference

Multi-Step Speed

H1-oo = 3

Multi-Step Speed 2

H1-oo = 4

Jog Reference

H1-oo = 6

Frequency Reference 1 (set in b1-01)

OFF

OFF

OFF

Frequency Reference 2

(d1-02 or input terminal A1, A2)

ON

OFF

OFF

Frequency Reference 3

(d1-03 or input terminal A1, A2)

OFF

ON

OFF

Frequency Reference 4 (d1-04)

ON

ON

OFF

Jog Frequency Reference (d1-17)

<1>

ON

<1> The Jog frequency overrides all other frequency references.

d1-04

d1-17

ON

ON

ON

ON

ON

Multi-step Speed Ref. 2

Jog Reference

Time

Multi-step Speed Ref. 1

Frequency

reference

d1-01

(A1)

d1-02

(A2)

d1-03

FWD (REV) Run/Stop

Figure 4.32 Preset Reference Timing Diagram

n

d2-03: Master Speed Reference Lower Limit

Sets a lower limit as a percentage of the maximum output frequency that will only affect a frequency reference entered from

the analog input terminals (A1 or A2) as the master speed reference. This is unlike parameter d2-02, which affects all frequency

references regardless of their source.

Note:

When lower limits are set to both parameters d2-02 and d2-03, the drive uses the greater of those two values as the lower limit.

No.

Parameter Name

Setting Range

Default

d2-03

Master Speed Reference Lower Limit

0.0 to 110.0%

0.0%

4.13 Advanced Drive Setup Adjustments

170

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual