13 advanced drive setup adjustments – Yaskawa AC Drive Z1000 User Manual

Page 172

Advertising
background image

Table 4.25 Predefined V/f Patterns

Setting

Specification

Characteristic

Application

0

50 Hz

Constant torque

For general purpose applications. Torque remains constant

regardless of changes to speed.

1

60 Hz

2

60 Hz (with 50 Hz base)

3

72 Hz (with 60 Hz base)

4

50 Hz, Variable torque 1

Variable torque

For fans, pumps, and other applications where the required

torque changes as a function of the speed.

5

50 Hz, Variable torque 2

6

50 Hz, Variable torque 3

7

50 Hz, Variable torque 4

8

50 Hz, Mid starting torque

High starting torque

Select high starting torque when:
• Wiring between the drive and motor exceeds 150 m.
• A large amount of starting torque is required.
• An AC reactor is installed.

9

50 Hz, High starting torque

A

60 Hz, Mid starting torque

B

60 Hz, High starting torque

C

90 Hz (with 60 Hz base)

Constant output

Output voltage is constant when operating at greater than

60 Hz.

D

120 Hz (with 60 Hz base)

E

180 Hz (with 60 Hz base)

F

<1>

60 Hz

Variable torque

Used for variable torque applications. The default setting is

the same as V/f pattern Setting 7.

<1> Setting F enables a custom V/f pattern by changing parameters E1-04 to E1-13. When the drive is shipped, the default values for parameters E1-04

to E1-13 are equal to predefined V/f pattern 1.

The following tables show details on predefined V/f patterns.

Predefined V/f Patterns for Models 2A0011 to 2A0017 and 4A0005 to 4A0011

The values in the following graphs are specific to 200 V class drives. Double the values for 400 V class drives.

Table 4.26 Constant Torque Characteristics, Settings 0 to 3

Setting = 0

50 Hz

Setting = 1

60 Hz

Setting = 2

60 Hz

Setting = 3

72 Hz

0

10.4

230

1.3 2.5

50

17.3

V

oltage (V)

Frequency (Hz)

0

10.4

17.3

230

1.5 3

60

V

oltage (V)

Frequency (Hz)

0

10.4

17.3

230

1.5 3

60

50

V

oltage (V)

Frequency (Hz)

0

10.4

17.3

230

1.5 3

72

60

V

oltage (V)

Frequency (Hz)

Table 4.27 Variable Torque Characteristics, Settings 4 to 7

Setting = 4

50 Hz

Setting = 5

50 Hz

Setting = 6

60 Hz

Setting = 7

60 Hz

0

9.2

230

1.3

25

50

40.3

V

oltage (V)

Frequency (Hz)

0

10.4

230

1.3

25

50

57.5

V

oltage (V)

Frequency (Hz)

0

9.2

230

1.5

30

60

40.3

V

oltage (V)

Frequency (Hz)

0

10.4

230

1.5

30

60

57.5

V

oltage (V)

Frequency (Hz)

Table 4.28 High Starting Torque, Settings 8 to B

Setting = 8

50 Hz

Setting = 9

50 Hz

Setting = A

60 Hz

Setting = B

60 Hz

0

12.7

230

1.3 2.5

50

21.9

V

oltage (V)

Frequency (Hz)

0

15

230

1.3 2.5

50

27.6

V

oltage (V)

Frequency (Hz)

0

12.7

230

1.5 3

60

21.9

V

oltage (V)

Frequency (Hz)

0

17.3

230

1.5 3

60

27.6

V

oltage (V)

Frequency (Hz)

4.13 Advanced Drive Setup Adjustments

172