Yaskawa AC Drive Z1000 User Manual

Page 136

Advertising
background image

n

E5-04: Number of Motor Poles

Sets the number of motor poles. Automatically set when the value is entered to T2-08 during Auto-Tuning.

No.

Parameter Name

Setting Range

Default

E5-04

Number of Motor Poles

2 to 48

Determined by

o2-04

n

E5-05: Motor Stator Resistance (r1)

Set the resistance for one motor phase. Do not enter the line-to-line resistance into E5-05 when measuring the resistance

manually.

No.

Parameter Name

Setting Range

Default

E5-05

Motor Stator Resistance

0.000 to 65.000 Ω

Determined by

o2-04

n

E5-06: Motor d-Axis Inductance (Ld)

Sets the d-Axis inductance in 0.01 mH units.

No.

Parameter Name

Setting Range

Default

E5-06

Motor d-Axis Inductance

0.00 to 300.00 mH

Determined by

o2-04

n

E5-07: Motor q-Axis Inductance (Lq)

Sets the q-Axis inductance in 0.01 mH units.

No.

Parameter Name

Setting Range

Default

E5-07

Motor q-Axis Inductance

0.00 to 600.00 mH

Determined by

o2-04

n

E5-09: Motor Induction Voltage Constant 1 (Ke)

Sets the induced peak voltage per phase in units of 0.1 mV/(rad/s) [electrical angle]. Set this parameter when using an IPM

motor with variable torque.

No.

Parameter Name

Setting Range

Default

E5-09

Motor Induction Voltage Constant 1

0.0 to 2000.0 mV/(rad/s)

Determined by

o2-04

Note:

Set E5-24 to 0 when setting E5-09. However, setting both E5-09 and E5-24 to 0 will trigger an alarm. An alarm will also be triggered if

neither E5-09 nor E5-24 are set to 0.

n

E5-24: Motor Induction Voltage Constant 2 (Ke)

Set the induced phase-to-phase rms voltage in units of 0.1 mV/(r/min) [mechanical angle]. Set this parameter when using an

SPM Motor.

No.

Parameter Name

Setting Range

Default

E5-24

Motor Induction Voltage Constant 2

0.0 to 6500.0 mV/(r/min)

Determined by

o2-04

Note:

Set E5-24 to 0.0 when setting E5-09. However, setting both E5-09 and E5-24 to 0.0 will trigger an alarm. An alarm will also be triggered

if neither E5-09 nor E5-24 are set to 0.0.

n

H3-03, H3-04: Terminal A1 Gain and Bias Settings

Parameter H3-03 sets the level of the selected input value that is equal to 10 Vdc (20 mA) input at terminal A1 (gain).
Parameter H3-04 sets the level of the selected input value that is equal to 0 V (4 mA, 0 mA) input at terminal A1 (bias).
Use both parameters to adjust the characteristics of the analog input signal to terminal A1.

No.

Name

Setting Range

Default

H3-03

Terminal A1 Gain Setting

-999.9 to 999.9%

100.0%

H3-04

Terminal A1 Bias Setting

-999.9 to 999.9%

0.0%

4.7 Basic Drive Setup Adjustments

136

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual