B.10 o: operator-related settings, O1: hoa keypad display selection – Yaskawa AC Drive Z1000 User Manual

Page 318

Advertising
background image

B.10 o: Operator-Related Settings

The o parameters set up the HOA keypad displays.

u

o1: HOA Keypad Display Selection

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

o1-01

(500)

Drive Mode Unit

Monitor Selection

User Monitor Sel

Selects the content of the last monitor that is shown when

scrolling through Drive Mode display. Enter the last three digits

of the monitor parameter number to be displayed: Uo-oo.

Default: 106

Range: 104 to

699

185

o1-02

(501)

User Monitor Selection

after Power Up

Power-On Monitor

1: Frequency Ref

2: FWD/REV

3: Output Freq

4: Output Current

5: User Monitor

1: Frequency reference (U1-01)

2: Direction

3: Output frequency (U1-02)

4: Output current (U1-03)

5: User Monitor

Default: 1

Range: 1 to 5

185

o1-03

(502)

HOA Keypad Operator

Display Selection

Display Unit Sel

0: 0.01 Hz

1: 0.01%

2: r/min

3: User Units

Sets the units the drive should use to display the frequency

reference and motor speed monitors.

0: 0.01 Hz

1: 0.01% (100% = E1-04)

2: r/min (calculated using the number of motor poles setting in

E2-04, E4-04, or E5-04)

3: User-selected units (set by o1-10 and o1-11)

Default: 0

Range: 0 to 3

186

o1-06

(517)

User Monitor Selection

Mode

Monitor Mode Sel

0: 3 Mon Sequential

1: 3 Mon Selectable

0: 3 Monitor Sequential

(Displays the next two sequential monitors)

1: 3 Monitor Selectable (o1-07 and o1-08 selected monitor are

shown)

Default: 0

Range: 0, 1

186

o1-07

(518)

Second Line Monitor

Selection

2nd Monitor Sel

Selects the monitor that is shown in the second line.

Enter the last three digits of the monitor parameter number to

be displayed: Uo-oo. For example, set "403" to display

monitor parameter U4-03.

Default: 102

Range: 101 to

699

186

o1-08

(519)

Third Line Monitor

Selection

3rd Monitor Sel

Selects the monitor that is shown in the third line.

Enter the last three digits of the monitor parameter number to

be displayed: Uo-oo. For example, set "403" to display

monitor parameter U4-03.

Default: 103

Range: 101 to

699

186

o1-09

(51C)

Frequency Reference

Display Units

Fref Disp Unit

0: WC

1: PSI

2: GPM

3: °F

4: CFM

5: CMH

6: LPH

7: LPS

8: Bar

9: Pa

10: °C

11: Mtr

12: Ft

13: LPM

14: CMM

15: Custom unit

16: No Unit

Sets unit display for the frequency reference parameters and

frequency related monitors when o1-03 > 40.

0: WC (Inch of water)

1: PSI (Pounds per square inch)

2: GPM (Gallons per minute)

3: F (Degrees Fahrenheit)

4: CFM (Cubic feet per minute)

5: CMH (Cubic meters per hour)

6: LPH (Liters per hour)

7: LPS (Liters per second)

8: Bar (Bar)

9: Pa (Pascal)

10: C (Degrees Celsius)

11: Mtr (Meters)

12: Ft (Feet)

13: LPM (Liters per minute)

14: CMM (Cubic meters per minute)

15: Custom units (Determined by o1-12)

16: None

Default: 16

Range: 0 to 16

186

o1-10

(520)

User-Set Display Units

Maximum Value

UserDisp Scaling

These settings define the display values when o1-03 is set to 3.

o1-10 sets the display value that is equal to the maximum output

frequency.

o1-11 sets the position of the decimal position.

Default:

<1>

Range: 1 to

60000

187

o1-11

(521)

User-Set Display Units

Decimal Display

UserDisp Dec

Default:

<1>

Range: 0 to 3

187

o1-13

(3105)

Frequency Reference

and Frequency Related

Monitor Custom Units 1

Fref Cust Unit 1

Sets the customer-specified unit display for the frequency

reference parameters and frequency related monitors when

o1-03 = 3 and o1-09 = 15 as custom units.

Default: 41

Range: 30 to 7A

187

o1-14

(3106)

Frequency Reference

and Frequency Related

Monitor Custom Units 2

Fref Cust Unit 2

Sets the customer-specified unit display for the frequency

reference parameters and frequency related monitors when

o1-03 = 3 and o1-09 = 15 as custom units

Default: 41

Range: 30 to 7A

187

B.10 o: Operator-Related Settings

318

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual

Advertising