Three-phase 200 v, Three-phase 400 v – Yaskawa AC Drive Z1000 User Manual
Page 28
n
Three-Phase 200 V
No.
Max Motor Capacity
kW (HP)
Rated Output Current
A
0011
2.2 (3)
10.6
0017
3.7 (5)
16.7
0024
5.5 (7.5)
24.2
0031
7.5 (10)
30.8
0046
11 (15)
46.2
0059
15 (20)
59.4
0075
18.5 (25)
74.8
0088
22 (30)
88
0114
30 (40)
114
0143
37 (50)
143
0169
45 (60)
169
0211
55 (75)
211
0273
75 (100)
273
0343
90 (125)
343
0396
110 (150)
396
n
Three-Phase 400 V
No.
Max Motor Capacity
kW (HP)
Rated Output Current
A
Input Voltage < 460 V
Input Voltage ≥ 460 V
0005
1.5 (2)
2.2 (3)
4.8
0008
3.0 (4)
3.7 (5)
7.6
0011
4.0 (5)
5.5 (7.5)
11
0014
5.5 (7.5)
7.5 (10)
14
0021
7.5 (10)
11 (15)
21
0027
11 (15)
15 (20)
27
0034
15 (20)
18.5 (25)
34
0040
18.5 (25)
22 (30)
40
0052
22 (30)
30 (40)
52
0065
30 (40)
37 (50)
65
0077
37 (50)
45 (60)
77
0096
45 (60)
55 (75)
96
0124
55 (75)
75 (100)
124
0156
75 (100)
90 (125)
156
0180
90 (125)
110 (150)
180
0240
110 (150)
150 (200)
240
0302
160 (220)
185 (250)
302
0361
185 (250)
220 (300)
361
0414
220 (300)
260 (350)
414
0480
250 (340)
300 (400)
480
0590
300 (400)
370 (500)
590
1.3 Model Number and Nameplate Check
28
YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual