Acceleration and deceleration times are too short

• Calculate the torque required during acceleration and for the inertia moment.
• If the torque level is not right for the load, take the following steps:
• Increase the acceleration and deceleration times (C1-01 to C1-04).
• Increase the capacity of the drive.

A special-purpose motor is being used, or the drive

is attempting to run a motor greater than the

maximum allowable capacity

• Check the motor capacity.
• Use a motor appropriate for the drive. Ensure the motor is within the allowable capacity range.

The current level increased due to Speed Search

after a momentary power loss or while attempting

to perform a fault restart

The alarm will only appear briefly. There is no need to take action to prevent the alarm from occurring

in such instances.

HOA Keypad Display

Minor Fault Name

inTLK

Interlock Open
ALM LED will not blink

Cause

Possible Solutions

BAS Interlock multi-function input is open

Check the cause of interlock.

HOA Keypad Display

Minor Fault Name

LT-1

Cooling Fan Maintenance Time
The cooling fan has reached its expected maintenance period and may need to be replaced.

Note:

An alarm output (H2-oo = 10) will only be triggered if both (H2-oo = 2F and H2-

oo = 10) are set.

Cause

Possible Solutions

The cooling fan has reached 90% of its expected

performance life

Replace the cooling fan and set o4-03 to 0 to reset the Maintenance Monitor.

HOA Keypad Display

Minor Fault Name

LT-2

Capacitor Maintenance Time

The main circuit and control circuit capacitors are nearing the end of their expected performance life.

Note:

An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.

Cause

Possible Solutions

The main circuit and control circuit capacitors have

reached 90% of their expected performance lives

Replace either the control board or the entire drive. For instructions on replacing the control board,

contact Yaskawa or your nearest sales representative.

HOA Keypad Display

Minor Fault Name

LT-3

Soft Charge Bypass Relay Maintenance Time
The DC bus soft charge relay is nearing the end of its expected performance life.

Note:

An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.

Cause

Possible Solutions

The DC bus soft charge relay has reached 90% of

expected performance life

Replace either the control board or the entire drive. For instructions on replacing the control board,

contact Yaskawa or your nearest sales representative.

HOA Keypad Display

Minor Fault Name

LT-4

IGBT Maintenance Time (50%)
IGBTs have reached 50% of their expected performance life.

Note:

An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.

Cause

Possible Solutions

IGBTs have reached 50% of their expected

performance life

Check the load, carrier frequency, and output frequency.

HOA Keypad Display

Minor Fault Name

oH

Heatsink Overheat
The temperature of the heatsink exceeded the overheat pre-alarm level set to L8-02 (90-100 °C).

Default value for L8-02 is determined by drive capacity (o2-04).

Cause

Possible Solutions

5.5 Alarm Detection

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual

221

5

Troubleshooting