Factory Recommended Branch Circuit Protection

WARNING! Fire Hazard. Install adequate branch circuit protection according to applicable local codes and this manual. Failure to comply

could result in fire and damage to the drive or injury to personnel. The device is suitable for use on a circuit capable of delivering not more

than 100,000 RMS symmetrical amperes, 240 Vac (200 V class) and 480 Vac (400 V class), when protected by branch circuit protection

devices specified in this manual.

Branch circuit protection shall be provided by any of the following: Non-time delay Class J, T, or CC fuses sized at 300% of the drive input

rating, or Time delay Class J, T, or CC fuses sized at 175% of the drive input rating, or MCCB sized at 200% maximum of the drive input

rating.

Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with UL508C.

Semiconductor protective type fuses are preferred. Alternate branch circuit protection devices are also listed in

Table 6.3

.

Table 6.3 Factory Recommended Z1000 AC Drive Branch Circuit Protection

Model

Nominal Output

Power (HP)

AC Drive Input

(A)

MCCB Rating (A)

<1>

Time Delay Fuse

Rating (A)

<2>

Non-time Delay

Fuse Rating (A)

<3>

Bussmann

Semiconductor

Fuse Model

(Fuse Ampere)

<4>

Three-Phase 200 V Class

2A0011

3

10.6

20

17.5

30

FWH-40B (40)

2A0017

5

16.7

30

25

50

FWH-50B (50)

2A0024

7.5

24.2

40

40

70

FWH-80B (80)

2A0031

10

30.8

60

50

90

FWH-100B (100)

2A0046

15

46.2

90

80

125

FWH-150B (150)

2A0059

20

59.4

110

100

175

FWH-175B (175)

2A0075

25

74.8

150

125

200

FWH-225A (225)

2A0088

30

88

175

150

250

FWH-225A (225)

2A0114

40

114

225

175

300

FWH-250A (250)

2A0143

50

143

250

250

400

FWH-275A (275)

2A0169

60

169

300

275

500

FWH-350A (350)

2A0211

75

211

400

350

600

FWH-400A (400)

2A0273

10

273

500

450

<5>

FWH-450A (450)

2A0343

125

343

600

600

FWH-600A (600)

2A0396

150

396

700

<5>

FWH-600A (600)

Three-Phase 400 V Class

4A0005

3

4.8

15

8

12

FWH-40B (40)

4A0008

5

7.6

15

12

20

FWH-40B (40)

4A0011

7.5

11

20

17.5

30

FWH-45B (45)

4A0014

10

14

25

20

40

FWH-45B (45)

4A0021

15

21

40

35

60

FWH-60B (60)

4A0027

20

27

50

45

80

FWH-60B (60)

4A0034

25

34

60

50

100

FWH-125B(125)

4A0040

30

40

75

70

110

FWH-150B (150)

4A0052

40

52

100

90

150

FWH-200B (200)

4A0065

50

65

125

110

175

FWH-225A (225)

4A0077

60

77

150

125

225

FWH-225A (225)

4A0096

75

96

175

150

275

FWH-225A (225)

4A0124

100

124

225

200

350

FWH-250A(250)

4A0156

125

156

300

250

450

FWH-300A (300)

4A0180

150

180

350

300

500

FWH-350A (350)

4A0240

200

240

450

400

<5>

FWH-400A (400)

4A0302

250

302

600

500

FWH-600A (600)

4A0361

300

346

600

600

1000

<6>

FWH-800A (800)

4A0414

350

410

800

700

1200

<6>

FWH-800A (800)

6.5 Installing Peripheral Devices

254