3.2 Standard Connection Diagram

Connect the drive and peripheral devices as shown in

Figure 3.1

. It is possible to set and run the drive via the HOA keypad

without connecting digital I/O wiring. This section does not discuss drive operation;

Refer to Start-Up Programming &

Operation on page 105

for instructions on operating the drive.

WARNING! Fire Hazard. Install adequate branch circuit protection according to applicable local codes and this manual. Failure to comply

could result in fire and damage to the drive or injury to personnel. The device is suitable for use on a circuit capable of delivering not more

than 100,000 RMS symmetrical amperes, 240 Vac (200 V class) and 480 Vac (400 V class), when protected by branch circuit protection

devices specified in this manual.

Branch circuit protection shall be provided by any of the following: Non-time delay Class J, T, or CC fuses sized at 300% of the drive input

rating, or Time delay Class J, T, or CC fuses sized at 175% of the drive input rating, or MCCB sized at 200% maximum of the drive input

rating.

NOTICE: When the input voltage is 440 V or higher or the wiring distance is greater than 100 meters, pay special attention to the motor

insulation voltage or use a drive duty motor. Failure to comply could lead to motor insulation breakdown.

NOTICE: Do not connect AC control circuit ground to drive enclosure. Improper drive grounding can cause control circuit malfunction.

Note:

The minimum load for the relay outputs M1-M2, M3-M4, M5-M6, and MA-MB-MC is 10 mA.

3.2 Standard Connection Diagram

62