Setting Examples

• Gain H3-03 = 200%, bias H3-04 = 0, terminal A1 as frequency reference input (H3-02 = 0):

A 10 Vdc input is equivalent to a 200% frequency reference and 5 Vdc is equivalent to a 100% frequency reference. Since

the drive output is limited by the maximum frequency parameter (E1-04), the frequency reference will be equal to E1-04

above 5 Vdc.

H3-01 = 0

10 V

5 V

0 V

Gain = 200 %

100 %

Frequency
reference

Bias = 0 %

E1-04

Figure 4.23 Frequency Reference Setting by Analog Input with Increased Gain

• Gain H3-03 = 100%, bias H3-04 = -25%, terminal A1 as frequency reference input:

An input of 0 Vdc will be equivalent to a -25% frequency reference.
When parameter H3-01 = 0, the frequency reference is 0% between 0 and 2 Vdc input.

0

2.0 V

10 V

100 %

Frequency
reference

-25%

H3-01 = 0

H3-01 = 1

H3-01 = 0

Analog Input

Voltage

Figure 4.24 Frequency Reference Setting by Analog Input with Negative Bias

n

H3-11, H3-12: Terminal A2 Gain and Bias Setting

Parameter H3-11 sets the level of the input value selected that is equal to 10 Vdc input or 20 mA input to terminal A2.
Parameter H3-12 sets the level of the input value selected that is equal to 0 V, 4 mA or 0 mA input at terminal A2.
Use both parameters to adjust the characteristics of the analog input signal to terminal A2. The setting works in the same way

as parameters H3-03 and H3-04 for analog input A1.

No.

Name

Setting Range

Default

H3-11

Terminal A2 Gain Setting

-999.9 to 999.9%

100.0%

H3-12

Terminal A2 Bias Setting

-999.9 to 999.9%

0.0%

n

L2-01: Momentary Power Loss Operation Selection

When a momentary power loss occurs (DC bus voltage falls below the level set in L2-05), the drive can automatically return

to the operation it was performing prior to the power loss based on certain conditions.

No.

Name

Setting Range

Default

L2-01

Momentary Power Loss Operation Selection

0 to 2

0

Setting 0: Disabled

If power is not restored within 15 ms, a Uv1 fault will result and the motor coasts to stop.

4.7 Basic Drive Setup Adjustments

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual

137