Yaskawa AC Drive Z1000 User Manual

Page 168

Advertising
background image

n

b5-45: Custom PI Output Monitor Setting 3

b5-14 shows Custom PI Output. b5-45 sets the minimum display value at zero speed. This function is effective when b5-42

is set to 0 (Linear).

No.

Name

Setting Range

Default

b5-45

Custom PI Output Monitor Setting 3

0

999.9

n

b5-46: PI Setpoint Monitor Unit Selection

Sets the HOA keypad display units in U5-01 and U5-04 when b5-20 is set to 3.

No.

Name

Setting Range

Default

b5-46

PI Setpoint Monitor Unit Selection

0 to 14

0

Setting 0: WC (Inch of Water)
Setting 1: PSI (Pounds per Square Inch)
Setting 2: GPM (Gallons per Minute)
Setting 3: F (Degrees Fahrenheit)
Setting 4: CFM (Cubic Feet per Minute)
Setting 5: CMH (Cubic Meters per Hour)
Setting 6: LPH (Liters per Hour)
Setting 7: LPS (Liters per Second)
Setting 8: Bar (Bar)
Setting 9: Pa (Pascal)
Setting 10: C (Degrees Celsius)
Setting 11: Mtr (Meters)
Setting 12: Ft (Feet)
Setting 13: LPM (Liters per Minute)
Setting 14: CMM (Cubic Meters per Minute)

n

b5-47: Reverse Operation Selection 2 by PI Output

Determines whether a negative PI output reverses the direction of drive operation. When the PI function is used to trim the

frequency reference (b5-01 = 3), this parameter has no effect and the PI output will not be limited

(same as b5-11 = 1).

No.

Name

Setting Range

Default

b5-47

Reverse Operation Selection 2 by PI Output

0, 1

1

Setting 0: Reverse Disabled

Negative PI output will be limited to zero and the drive output will be stopped.

Setting 1: Reverse Enabled

Negative PI output will cause the drive to run in the opposite direction.

n

C2-01 and C2-02: S-Curve Characteristics

C2-01 and C2-02 set separate S-curves for each section of the acceleration or deceleration.

No.

Parameter Name

Setting Range

Default

C2-01

S-Curve Characteristic at Accel Start

0.00 to 10.00 s

Determined by

A1-02

C2-02

S-Curve Characteristic at Accel End

0.20 s

Figure 4.30

illustrates S-curve application.

4.13 Advanced Drive Setup Adjustments

168

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual