B.8 L: Protection Function

L parameters provide protection to the drive and motor, including control during momentary power loss, Stall Prevention,

frequency detection, fault restarts, overtorque detection, and other types of hardware protection.

u

L1: Motor Protection

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L1-01

(480)

Motor Overload

Protection Selection

Mtr OL Charact

0: OL1 Disabled

1: VT Motor

4: PM Motor

0: Disabled

1: General purpose motor (standard fan cooled)

4: PM motor with variable torque

The drive may not be able to provide protection when using

multiple motors, even if overload is enabled in L1-01. Set L1-01

to 0 and install separate thermal relays to each motor.

Default:

<1>

Range: 0, 1, 4

L1-02

(481)

Motor Overload

Protection Time

MOL Time Const

Sets the motor thermal overload protection (oL1) time.

Default: 1.0 min

Min.: 1.0

Max.: 5.0

L1-03

(482)

Motor Overheat Alarm

Operation Selection

(PTC input)

Mtr OH Alarm Sel

0 : Ramp to Stop

1: Coast to Stop

2: Fast-Stop

3: Alarm only

Sets operation when the motor temperature analog input

(H3-02 or H3-10 = E) exceeds the alarm level.

0: Ramp to stop

1: Coast to stop

2: Fast Stop (decelerate to stop using the deceleration time in

C1-09)

3: Alarm only (“oH3” will flash)

Default: 3

Range: 0 to 3

L1-04

(483)

Motor Overheat Fault

Operation Selection

(PTC input)

Mtr OH Fault Sel

0 : Ramp to Stop

1: Coast to Stop

2: Fast-Stop

Sets stopping method when the motor temperature analog input

(H3-02, or H3-10 = E) exceeds the oH4 fault level.

0: Ramp to stop

1: Coast to stop

2: Fast Stop (decelerate to stop using the deceleration time in

C1-09)

Default: 1

Range: 0 to 2

L1-05

(484)

Motor Temperature

Input Filter Time (PTC

input)

Mtr Temp Filter

Adjusts the filter for the motor temperature analog input

(H3-02, or H3-10 = E).

Default: 0.20 s

Min.: 0.00

Max.: 10.00

L1-08

(1103)

<2>

oL1 Current Level

oL1 Current Lvl

Sets the reference current for motor thermal overload detection

for the motor in amperes.

Default:

<3>

Min.: 10% of

drive rated

current

Max.: 150% of

drive rated
current

<4>

L1-13

(46D)

Continuous

Electrothermal

Operation Selection

Mtr OL Mem Sel

0: Disabled

1: Enabled

2: Enabled(RTC)

0: Disabled

1: Enabled

2: Enable using Real Time Clock

Default: 1

Range: 0 to 2

<1> Default setting is determined by parameter A1-02, Control Method Selection.
<2> Available in drive software versions PRG: 1016 and later.
<3> Default setting is determined by parameters o2-04, Drive Model Selection, and C6-01, Drive Duty Selection.
<4> The number of decimal places in the parameter value depends on the drive model. This value has two decimal places (0.01 A) if the drive is set for

a maximum applicable motor capacity up to and including 11 kW, 2A0031, 4A0021 (input voltage 460 V or higher) or 4A0027 (input voltage lower
than 460 V) and one decimal place (0.1 A) if the maximum applicable motor capacity is higher than 11 kW, 2A0046, 4A0027 (input voltage 460
V or higher) or 4A0034 (input voltage lower than 460 V) .

B.8 L: Protection Function

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual

309

B