Insulation Tolerance

NOTICE: Consider motor voltage tolerance levels and motor insulation in applications with an input voltage of over 440 V or particularly

long wiring distances.

High-Speed Operation

NOTICE: Problems may occur with the motor bearings and dynamic balance of the machine when operating a motor beyond its rated speed.

Contact the motor or machine manufacturer.

Torque Characteristics

Torque characteristics differ compared to operating the motor directly from line power. The user should have a full

understanding of the load torque characteristics for the application.

Vibration and Shock

The drive allows selection of high carrier PWM control and low carrier PWM. Selecting high carrier PWM can help reduce

motor oscillation.
Take particular caution when adding a variable speed drive to an application running a motor from line power at a constant

speed. If resonance occurs, install shock-absorbing rubber around the base of the motor and enable the Jump frequency selection

to prevent continuous operation in the resonant frequency range.

Audible Noise

The audible noise of the motor varies based on the carrier frequency setting. However, drive current derating may be required.

When using a high carrier frequency, audible noise from the motor is comparable to the motor noise generated when running

from line power.

n

Synchronous Motors

• Contact Yaskawa or a Yaskawa agent when planning to use a synchronous motor not endorsed by Yaskawa.
• Use a standard induction motor when running multiple synchronous motors simultaneously. A single drive does not have

this capability.

• A synchronous motor may rotate slightly in the opposite direction of the Run command at start depending on parameter

settings and rotor position.

• The amount of generated starting torque differs depending on the control mode and motor type. Set up the motor with the

drive after verifying the starting torque, allowable load characteristics, impact load tolerance, and speed control range.
Contact Yaskawa or a Yaskawa agent when planning to use a motor that does not fall within these specifications:

• In Open Loop Vector Control for PM motors, braking torque is less than 125% when running between 20% and 100% speed.

Braking torque drops to less than 50% when running at less than 20% speed.

• In Open Loop Vector Control for PM motors, the allowable load inertia moment is approximately 50 times higher than the

motor inertia moment.
Contact Yaskawa or a Yaskawa agent for questions concerning applications with a larger inertia moment.

• To restart a coasting motor rotating below 100 Hz, use the Speed Search function if the motor cable is not too long. If the

motor cable is relatively long, stop the motor using Short Circuit Braking.

n

Specialized Motors

Multi-Pole Motor

The rated current of a multi-pole motor differs from that of a standard motor, so be sure to check the maximum current when

selecting a drive. Always stop the motor before switching between the number of motor poles. The motor will coast to stop if

a regen overvoltage (ov) fault occurs or if overcurrent (oC) protection is triggered.

Submersible Motor

The rated current of a submersible motor is greater than that of a standard motor, so select the drive capacity accordingly. Use

a motor cable large enough to avoid decreasing the maximum torque level from voltage drop caused by a long motor cable.

Explosion-Proof Motor

The motor and the drive must be tested together to be certified as explosion-proof. The drive is not designed for explosion-

proof areas.

Geared Motor

Make sure that the gear and the lubricant are rated for the desired speed range to avoid gear damage when operating at low

speeds or very high speeds. Consult with the manufacturer for applications that require operation outside the rated speed range

of the motor or gear box.

i.2 General Safety

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual