Yaskawa AC Drive Z1000 User Manual

Page 267

Advertising
background image

u

Three-Phase 200 V Class Drive Models 2A0114 to 2A0396

Table A.2 Power Ratings Continued (Three-Phase 200 V Class)

Item

Specification

CIMR-Zo2A

0114

0143

0169

0211

0273

0343

0396

Maximum

Applicable

Motor

Capacity

<1>

HP

40

50

60

75

100

125

150

kW

30

37

45

55

75

90

110

Input

Input Current (A)

<2>

114

143

169

211

273

343

396

Rated Voltage

Rated Frequency

Three-phase 200 to 240 Vac 50/60 Hz

Allowable Voltage Fluctuation

-15 to 10%

Allowable Frequency Fluctuation

±5%

Minimum Power Supply Capacity (kVA)

48

60

71

88

114

143

165

Output

Rated Output Capacity (kVA)

<3>

45

57

67

84

109

137

158

Rated Output Current (A)

114

<4>

143

<4>

169

<4>

211

<4>

273

<4>

343

<5>

396

<5>

Overload Tolerance

110% of rated output current for 60 s

140% of rated output current for 0.5 s

Carrier Frequency

User adjustable between 1 and 12.5 kHz

(Maximum Frequency varies with Rated Output Capacity)

Maximum Output Voltage (V)

Three-phase 200 to 240 V (proportional to input voltage)

Maximum Output Frequency (Hz)

240 Hz

Harmonics

Reduction

DC Link Choke

Built-in

EMC

Filter (IEC/EN 61800-3 Category 2)

Built-in

External

<1> The motor capacity (HP) refers to an NEC Table 430.250 208 V motor. The rated output current of the drive output amps should be equal to or

greater than the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.

<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring

connections, and power supply impedance.

<3> Rated motor capacity is calculated with a rated output voltage of 230 V.
<4> Carrier frequency is set to 5 kHz. Current derating is required to raise the carrier frequency.
<5> Carrier frequency is set to 2 kHz. Current derating is required to raise the carrier frequency.

A.1 Power Ratings

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual

267

A

Specifications

Advertising