b5-17: PI Accel/Decel Time

The PI acceleration/deceleration time is applied on the PI setpoint value.
When the setpoint changes quickly, the normal C1-oo acceleration times reduce the responsiveness of the system as they

are applied after the PI output. The PI accel/decel time helps avoid the hunting and overshoot and undershoot that can result

from the reduced responsiveness.
The PI acceleration/deceleration time can be canceled using a digital input programmed for “PI SFS cancel” (H1-oo = 34).

No.

Name

Setting Range

Default

b5-17

PI Accel/Decel Time

0.0 to 6000.0 s

0.0 s

n

b5-18: PI Setpoint Selection

Enables or disables parameter b5-19 for PI setpoint.

No.

Parameter Name

Setting Range

Default

b5-18

PI Setpoint Selection

0, 1

0

Setting 0: Disabled

Parameter b5-19 is not used as the PI setpoint.

Setting 1: Enabled

Parameter b5-19 is used as PI setpoint.

n

b5-19: PI Setpoint Value

Used as the PI setpoint if parameter b5-18 = 1.

No.

Name

Setting Range

Default

b5-19

PI Setpoint Value

0.00 to 600.00%

0.00%

Note:

Unit and resolution for b5-19 is determined by b5-20, b5-39, and b5-46.

The following conditions apply to drives with software PRG: 1014 and later. Parameter b5-19 is internally limited to b5-38.

Changing b5-20, b5-38 and b5-39 will not automatically update the value of b5-19.

n

b5-20: PI Setpoint Scaling

Determines the units for the PI Setpoint Value (b5-19) and monitors U5-01 and U5-04.

No.

Parameter Name

Setting Range

Default

b5-20

PI Setpoint Scaling

0 to 3

1

Setting 0: Hz

The setpoint and PI monitors are displayed in Hz with a resolution of 0.01 Hz.

Setting 1: %

The setpoint and PI monitors are displayed as a percentage with a resolution of 0.01%.

Setting 2: r/min

The setpoint and PI monitors are displayed in r/min with a resolution of 1 r/min.

Setting 3: User Defined

Parameters b5-38 and b5-39 determine the units and resolution used to display the values the setpoint in b5-19, and PI monitors

U5-01 and U5-04.

n

b5-21: PI Sleep Input Source

Selects the Sleep Function characteristic action. When b5-21 is set to 1, the Sleep Function Start Level (b5-15) is compared

to the output of the drive (Speed Command after PI Block). Use this setting for open loop control.
The Sleep Function Start Level (b5-15) can be compared to the drive input or setpoint by setting b5-21 to 0.
When b5-21 is set to 2, a variation of the Sleep Function called “Snooze” is enabled. See parameters b5-22 to b5-27 for details.

No.

Parameter Name

Setting Range

Default

b5-21

PI Sleep Input Source

0 to 2

1

4.13 Advanced Drive Setup Adjustments

164