Setting 0: PI Setpoint
Setting 1: SFS Input
Setting 2: Snooze

n

b5-22: PI Snooze Level

Sets the PI Snooze function start level as a percentage of maximum frequency.

No.

Parameter Name

Setting Range

Default

b5-22

PI Snooze Level

0 to 100%

0%

n

b5-23: PI Snooze Delay Time

Sets the PI Snooze function delay time in seconds.

No.

Parameter Name

Setting Range

Default

b5-23

PI Snooze Delay Time

0 to 2600 s

0 s

n

b5-24: PI Snooze Deactivation Level

When the PI feedback drops below this level, normal operation starts again. Sets as a percentage of maximum frequency.

No.

Parameter Name

Setting Range

Default

b5-24

PI Snooze Deactivation Level

0 to 100%

0%

n

b5-25: PI Setpoint Boost Setting

Temporary increase of PI setpoint to create an overshoot of the intended PI setpoint.

No.

Parameter Name

Setting Range

Default

b5-25

PI Setpoint Boost Setting

0 to 100%

0%

n

b5-26: PI Maximum Boost Time

Associated with the Snooze Function. In cases where the temporary PI Setpoint (intended PI setpoint + PI Setpoint Boost)

cannot be reached within the PI Maximum Boost Time (b5-26), the Setpoint Boost is interrupted and the Drive output is turned

off.

No.

Parameter Name

Setting Range

Default

b5-26

PI Maximum Boost Time

0 to 2600 s

0 s

n

b5-27: PI Snooze Feedback Level

The second method of initiating the Snooze Function. The drive output shuts off when the PI feedback level exceeds the PI

Snooze Feedback Level (b5-27).
Normal drive and PI operation return after the PI feedback drops below the PI Snooze Deactivation Level (b5-24). Snooze

activates when both b5-22 and b5-27 conditions are met. There is no time delay for deactivation.
Sets as a percentage of maximum frequency.

No.

Parameter Name

Setting Range

Default

b5-27

PI Snooze Feedback Level

0 to 100%

60%

n

b5-28: PI Feedback Function Selection

When b5-28 is set to 1, the square root of the PI feedback is compared to the PI Setpoint to determine appropriate drive output

to properly regulate the system.
This is helpful in cases where the measured feedback is pressure, but the PI loop needs to regulate flow.

No.

Parameter Name

Setting Range

Default

b5-28

PI Feedback Function Selection

0, 1

0