Figure 4.21 Frequency Reference: Upper and Lower Limits

n

E1-01: Input Voltage Setting

Adjusts the levels of some protective features of the drive (overvoltage, Stall Prevention, etc.). Set this parameter to the nominal

voltage of the AC power supply.

NOTICE: Set parameter E1-01 to match the input voltage of the drive. Drive input voltage (not motor voltage) must be set in E1-01 for the

protective features to function properly. Failure to set the correct drive input voltage will result in improper drive operation.

No.

Parameter Name

Setting Range

Default

E1-01

Input Voltage Setting

190 to 240 V

<1>

230 V

<1>

<1> Values shown are specific to 200 V class drives. Double the value for 400 V class drives.

E1-01 Related Values

The input voltage setting determines the overvoltage and undervoltage detection levels, the KEB function, and the overvoltage

suppression function.

Voltage

Setting Value of E1-01

(Approximate Values)

Uv Detection Level (L2-05)

200 V Class

All settings

190 V

400 V Class

Setting > 460 V

440 V

Setting ≥ 400 V

380 V

Setting < 400 V

350 V

n

V/f Pattern Settings E1-04 to E1-13

If E1-03 is set to a preset V/f pattern (i.e., a value other than F), the user can monitor the V/f pattern in parameters E1-04

through E1-13. To create a new V/f pattern, set E1-03 to F.

Refer to V/f Pattern on page 135

for an example custom V/f

pattern.

Note:

Certain E1-oo parameters might not be visible depending on the control mode.

Refer to Parameter List on page 279

for details.

No.

Parameter Name

Setting Range

Default

E1-04

Maximum Output Frequency

40.0 to 240.0 Hz

<1>

E1-05

Maximum Voltage

0.0 to 255.0 V

<2>

<1>

E1-06

Base Frequency

0.0 to 240.0 kHz

<1>

E1-07

Middle Output Frequency

0.0 to 240.0 kHz

<1>

E1-08

Middle Output Frequency Voltage

0.0 to 255.0 V

<2>

<1>

E1-09

Minimum Output Frequency

0.0 to 240.0 kHz

<1>

E1-10

Minimum Output Frequency Voltage

0.0 to 255.0 V

<2>

<1>

E1-11

Middle Output Frequency 2

0.0 to 240.0 kHz

0.0 Hz

<3>

E1-12

Middle Output Frequency Voltage 2

0.0 to 255.0 V

<2>

0.0 V

<3>

E1-13

Base Voltage

0.0 to 255.0 V

<2>

0.0 V

<1> Default setting is determined by the control mode.
<2> Values shown are specific to 200 V class drives. Double the value for 400 V class drives.
<3> Parameter ignored when E1-11 and E1-12 are set to 0.0.