E2: motor parameters, E5: pm motor settings – Yaskawa AC Drive Z1000 User Manual

Page 295

Advertising
background image

<1> Values shown are specific to 200 V class drives. Double the value for 400 V class drives.
<2> Parameter setting value is not reset to the default value when the drive is initialized.
<3> Default setting is dependent on parameters A1-02, Control Model Selection and o2-04, Drive Model Selection.
<4> Default setting is dependent on parameter o2-04, Drive Model Selection.
<5> When Auto-Tuning is performed, E1-13 and E1-05 will be set to the same value.
<6> Parameter ignored when E1-11 (Motor 1 Mid Output Frequency 2) and E1-12 (Motor 1 Mid Output Frequency Voltage 2) are set to 0.0.

u

E2: Motor Parameters

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

E2-01

(30E)

Motor Rated Current

Motor Rated FLA

Sets the motor nameplate full load current in amps.

Automatically set during Auto-Tuning.

Default:

<1>

Min.: 10% of

drive rated

current

Max.: 200% of

drive rated
current

<2>

135

E2-02

(30F)

Motor Rated Slip

Motor Rated Slip

Sets the motor rated slip. Automatically set during

Auto-Tuning.

Default:

<1>

Min.: 0.00 Hz

Max.: 20.00 Hz

E2-03

(310)

Motor No-Load Current No-Load Current

Sets the no-load current for the motor. Automatically set during

Auto-Tuning.

Default:

<1>

Min.: 0 A
Max.: E2-01

<2>

E2-04

(311)

Number of Motor Poles Number of Poles

Sets the number of motor poles. Automatically set during

Auto-Tuning.

Default: 4

Min.: 2

Max.: 48

E2-05

(312)

Motor Line-to-Line

Resistance

Term Resistance

Sets the phase-to-phase motor resistance. Automatically set

during Auto-Tuning.

Default:

<1>

Min.: 0.000 Ω

Max.: 65.000 Ω

E2-10

(317)

Motor Iron Loss for

Torque Compensation

Motor Iron Loss

Sets the motor iron loss.

Default:

<1>

Min.: 0 W

Max.: 65535 W

E2-11

(318)

Motor Rated Power

Mtr Rated Power

Sets the motor rated power in kilowatts (1 HP = 0.746 kW).

Automatically set during Auto-Tuning.

Default:

<1>

Min.: 0.00 kW

Max.: 370.00 kW

135

<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> The number of decimal places in the parameter value depends on the drive model. This value has two decimal places (0.01 A) if the drive is set for

a maximum applicable motor capacity up to and including 11 kW, 2A0031, 4A0021 (input voltage 460 V or higher) or 4A0027 (input voltage lower
than 460 V) and one decimal place (0.1 A) if the maximum applicable motor capacity is higher than 11 kW, 2A0046, 4A0027 (input voltage 460
V or higher) or 4A0034 (input voltage lower than 460 V) .

u

E5: PM Motor Settings

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

E5-02

(32A)

<1>

Motor Rated Power

PM Mtr Capacity

OLV/PM

OLV/PM

Sets the rated capacity of the motor.

Default:

<2>

Min.: 0.10 kW

Max.: 370.00 kW

135

E5-03

(32B)

<1>

Motor Rated Current

PM Mtr Rated FLA

OLV/PM

OLV/PM

Sets the motor rated current.

Default:

<2>

Min: 10% of

drive rated

current

Max: 200% of

drive rated
current

<3>

135

E5-04

(32C)

<1>

Number of Motor Poles PM Motor Poles

OLV/PM

OLV/PM

Sets the number of motor poles.

Default:

<2>

Min.: 2

Max.: 48

136

B.5 E: Motor Parameters

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual

295

B

Parameter List

Advertising