Cause

Possible Solution

Parameter settings are not appropriate for the load Check the settings of parameters L6-02 and L6-03.
There is a fault on the machine side

Check the load for any problems.

HOA Keypad Display

Fault Name

UL6

Motor Underload
The weight of the load has fallen below the underload curve defined in L6-14.

Cause

Possible Solution

The output current has fallen below the motor

underload curve defined in L6-14 for longer than

the time set to L6-03

Adjust the value set to L6-14 so that output current remains above the motor underload curve during

normal operation.

HOA Keypad Display

Fault Name

Uv1

DC Bus Undervoltage
Voltage in the DC bus fell below the undervoltage detection level (L2-05).
• For 200 V class drives: approximately 190 V
• For 400 V class drives: approximately 440 when using input voltages 460 V or higher (350 V when

E1-01 is less than 400, and 380 V when 400V ≤ E1-01 < 460 V )

The fault is output only if L2-01 is set to 0 or 1 and the DC bus voltage has fallen below the level set

to L2-05 for longer than the time set to L2-02.

Cause

Possible Solution

Input power phase loss

• The main circuit drive input power is wired incorrectly.
• Correct the wiring.

One of the drive input power wiring terminals is

loose

• Ensure there are no loose terminals.
• Apply the tightening torque specified in this manual to fasten the terminals.

Refer to Wire Gauges

and Tightening Torque on page 83

for details.

There is a problem with the voltage from the drive

input power

• Check the voltage.
• Correct the voltage to be within the range listed in drive input power specifications.
• If there is no problem with the power supply to the main circuit, check for problems with the main

circuit magnetic contactor.

The power has been interrupted

Correct the drive input power.

The main circuit capacitors are worn

• Check the maintenance time for the capacitors (U4-05).
• Replace either the control board or the entire drive if U4-05 exceeds 90%. For instructions on

replacing the control board, contact Yaskawa or a Yaskawa representative.

The relay or contactor on the soft-charge bypass

circuit is damaged

• Cycle power to the drive and see if the fault reoccurs.
• If the problem continues, replace either the control board or the entire drive. For instructions on

replacing the control board, contact Yaskawa or a Yaskawa representative.

• Check monitor U4-06 for the performance life of the soft-charge bypass.
• Replace either the control board or the entire drive if U4-06 exceeds 90%. For instructions on

replacing the control board, contact Yaskawa or a Yaskawa representative.

HOA Keypad Display

Fault Name

Uv2

Control Power Supply Voltage Fault
Voltage is too low for the control drive input power.

Cause

Possible Solution

Internal circuitry is damaged

• Cycle power to the drive. Check if the fault reoccurs.
• If the problem continues, replace either the control board or the entire drive. For instructions on

replacing the control board, contact Yaskawa or a Yaskawa representative.

HOA Keypad Display

Fault Name

Uv3

Undervoltage 3 (Soft-Charge Circuit Fault)
The soft-charge bypass circuit failed.

Cause

Possible Solution

The relay or contactor on the soft-charge bypass

circuit is damaged

• Cycle power to the drive and see if the fault reoccurs.
• If the problem continues, replace either the control board or the entire drive. For instructions on

replacing the control board, contact Yaskawa or a Yaskawa representative.

• Check monitor U4-06 for the performance life of the soft-charge bypass.
• Replace either the control board or the entire drive if U4-06 exceeds 90%. For instructions on

replacing the control board, contact Yaskawa or a Yaskawa representative.

5.4 Fault Detection

216

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual

Advertising