S6: z1000 protection – Yaskawa AC Drive Z1000 User Manual

Page 326

Advertising
background image

u

S6: Z1000 Protection

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

S6-01

(3236)

Emergency Override

Speed

E Override Speed

Sets the speed command used in Emergency Override mode when

S6-02 = 0.

Default: 0.00

Hz

Min.: 0.00

Max.: 240.00

S6-02

(3237)

Emergency Override

Reference Selection

E OverrideRefSel

0: Use S6-01 Ref

1: Use AUTO Ref

Selects the frequency reference source for the Emergency

Override function (H1-oo= AF or B0).

0: Use S6-01 Reference

1: Use AUTO Reference

Note:

In drive software versions PRG: 1013 and earlier,

if the CALL alarm is displayed, the Emergency

Override Forward (H1-0o = AF) and Emergency

Override Reverse (H1-0o = B0) inputs are

ignored. In drive software versions PRG: 1014 and

later, the Emergency Override inputs will function

even if the CALL alarm is displayed.

Default: 0

Range: 0, 1

S6-03

(3238)

ov2 Detect Time

ov2 Detect Time

Sets the detection time of ov2 in 0.1 s increments.

Default: 10.0 s

Min.: 0.0

Max.: 1200.0

S6-04

(3239)

Main Contactor and

Cooling Fan Power

Supply Failure

FAN1 Fault Sel

0: Ramp to Stop

1: Coast to stop

2: Fast-Stop

Determines the action the drive should take when a fault occurs

with the external cooling fan.

0: Ramp to stop

1: Coast to Stop

2: Fast Stop (decelerate to stop using the deceleration time in

C1-09)

Default: 1

Range: 0 to 2

S6-07

(323C)

Output Phase Loss

Detection Level for

Dynamic Audible Noise

Control

Outp Ph Loss Lv1

Sets the output phase loss detection level for Dynamic Audible

Noise Control. Decrease the setting in steps of 10% when output

phase loss is detected erroneously. This setting rarely needs to be

changed.

Default:

100.0%

Min.: 10.0

Max.: 100.0

B.11 S: Special Application

326

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual