U4: maintenance monitors, For a complete list of u4 – Yaskawa AC Drive Z1000 User Manual

Page 333

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U3-48

(3026)

Date Year at 10th Most

Recent Fault

Fault 10 YYYY

Displays the year when the tenth most recent fault occurred.

No signal output

available

U3-49

(3027)

Date Month and Day at

10th Most Recent Fault

Fault 10 MMDD

Displays the date and day when the tenth most recent fault

occurred.

No signal output

available

U3-50

(3028)

Time Hours and Minutes

at 10th Most Recent

Fault 10 HHMM

Displays the time when the tenth most recent fault occurred.

No signal output

available

u

U4: Maintenance Monitors

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U4-01

(4C)

Cumulative Operation

Time

Drv Elapsed Time

Displays the cumulative operation time of the drive. The value

for the cumulative operation time counter can be reset in

parameter o4-01. Use parameter o4-02 to determine if the

operation time should start as soon as the power is switched on

or only while the Run command is present. The maximum

number displayed is 99999, after which the value is reset to 0.

No signal output

available

1 h

U4-02

(75)

Number of Run

Commands

RUN Cmd Counter

Displays the number of times the Run command is entered. Reset

the number of Run commands using parameter o4-13. This value

will reset to 0 and start counting again after reaching 65535.

No signal output

available

1 Time

U4-03

(67)

Cooling Fan Operation

Time

Fan Elapsed TIme

Displays the cumulative operation time of the cooling fan. The

default value for the fan operation time is reset in parameter

o4-03. This value will reset to 0 and start counting again after

reaching 99999.

No signal output

available

1 h

U4-04

(7E)

Cooling Fan

Maintenance

Fan Life Mon

Displays main cooling fan usage time as a percentage of its

expected performance life. Parameter o4-03 can be used to reset

this monitor.

No signal output

available

1%

U4-05

(7C)

Capacitor Maintenance Cap Life Mon

Displays main circuit capacitor usage time as a percentage of their

expected performance life. Parameter o4-05 can be used to reset

this monitor.

No signal output

available

1%

U4-06

(7D6)

Soft Charge Bypass

Relay Maintenance

ChgCirc Life Mon

Displays the soft charge bypass relay maintenance time as a

percentage of its estimated performance life. Parameter o4-07 can

be used to reset this monitor.

No signal output

available

1%

U4-08

(68)

Heatsink Temperature

Heatsink Temp

Displays the heatsink temperature.

10 V: 100 °C

1 °C

U4-09

(5E)

LED Check

LED Oper Check

Lights all segments of the LED to verify that the display is

working properly.

No signal output

available

U4-10

(5C)

kWh, Lower 4 Digits

kWh Lower 4 dig

Monitors the drive output power. The value is shown as a 9-digit

number displayed across two monitor parameters, U4-10 and

U4-11.

Example:

12345678.9 kWh is displayed as:

U4-10: 678.9 kWh

U4-11: 12345 MWh

No signal output

available

1 kWh

U4-11

(5D)

kWh, Upper 5 Digits

kWh Upper 5 dig

No signal output

available

1 MWh

U4-13

(7CF)

Peak Hold Current

Current PeakHold

Displays the highest current value that occurred during run.

No signal output

available

0.01 A

<1>

U4-14

(7D0)

Peak Hold Output

Frequency

Freq@ I PeakHold

Displays the output frequency when the current value shown in

U4-13 occurred.

No signal output

available

0.01 Hz

U4-16

(7D8)

Motor Overload

Estimate (oL1)

Motor OL1 Level

Shows the value of the motor overload detection accumulator.

100% is equal to the oL1 detection level.

10 V: 100%

0.1%

B.13 U: Monitors

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual

333