No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U4-18

(7DA)

Frequency Reference

Source Selection

Reference Source

Displays the source for the frequency reference as XY-nn.

X: indicates which reference is used:

0 = OFF

1 = AUTO

2 = HAND

Y-nn: indicates the reference source

0-01 = HOA keypad

1-00 = Analog (not assigned)

1-01 = Analog (terminal A1)

1-02 = Analog (terminal A2)

2-02 to 17 = Multi-step speed (d1-02 to 17)

3-01 = MEMOBUS/Modbus communications

4-01 = Communication option card

9-01 = Up/Down

No signal output

available

U4-19

(7DB)

Frequency Reference

from MEMOBUS/

Modbus Comm.

MEMOBUS Freq Ref

Displays the frequency reference provided by MEMOBUS/

Modbus (decimal).

No signal output

available

0.01%

U4-20

(7DC)

Option Frequency

Reference

Option Freq Ref

Displays the frequency reference input by an option card

(decimal).

No signal output

available

U4-21

(7DD)

Run Command Source

Selection

Run Cmd Source

Displays the source for the Run command as XY-nn.

X: Indicates which Run source is used:

0 = OFF

1 = AUTO

2 = HAND

Y: Input power supply data

0 = HOA keypad

1 = External terminals

3 = Serial communications (APOGEE FLN, BACnet,

MEMOBUS/Modbus, or Metasys N2)

4 = Communication option card

nn: Run command limit status data

00: No limit status.

01: Run command was left on when stopped in the PRG mode

02: Run command was left on when switching from LOCAL to

REMOTE operation

03: Waiting for soft charge bypass contactor after power up (Uv

or Uv1 flashes after 10 s)

04: Waiting for “Run command prohibited” time period to end

05: Fast Stop (digital input, HOA keypad)

06: b1-17 (Run command given at power-up)

07: During baseblock while coast to stop with timer

08: Frequency reference is below minimal reference during

baseblock

09: Waiting for Enter command

No signal output

available

U4-22

(7DE)

MEMOBUS/Modbus

Communications

Reference

MEMOBUS Ref Reg

Displays the drive control data set by MEMOBUS/Modbus

communications register no. 0001H as a four-digit hexadecimal

number.

No signal output

available

U4-23

(7DF)

Communication Option

Card Reference

Option Ref Reg

Displays drive control data set by an option card as a four-digit

hexadecimal number.

No signal output

available

<1> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.

u

U5: PI Monitors

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U5-01

(57)

PI Feedback

PID Feedback 1

Displays the PI feedback value.

10 V: 100%

0.01%

U5-02

(63)

PI Input

PID Input

Displays the amount of PI input (deviation between PI setpoint

and feedback).

10 V: 100%

0.01%

U5-03

(64)

PI Output

PID Output

Displays PI control output.

10 V: 100%

0.01%

U5-04

(65)

PI Setpoint

PID Setpoint

Displays the PI setpoint.

10 V: 100%

0.01%

U5-05

(7D2)

PI Differential Feedback PID Feedback 2

Displays the second PI feedback value if differential feedback is

used (H3-oo = 16).

10 V: 100%

0.01%

B.13 U: Monitors

334

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual