1.2 General Description

u

Z1000 Model Selection

Refer to

Table 1.1

for drive selection depending on the motor power.

Note:

The models and capacities in shown here are based on standard settings and operation conditions. Higher carrier frequencies and higher

ambient temperatures require derating.

Table 1.1 Z1000 Models

Motor Capacity kW (HP)

Three-Phase 200 V Class

Model CIMR-Zo

Rated Output Current (A)

2.2 (3)

2A0011

10.6

<1>

3.7 (5)

2A0017

16.7

<1>

5.5 (7.5)

2A0024

24.2

<1>

7.5 (10)

2A0031

30.8

<1>

11 (15)

2A0046

46.2

<1>

15 (20)

2A0059

59.4

<1>

18.5 (25)

2A0075

74.8

<1>

22 (30)

2A0088

88

<1>

30 (40)

2A0114

114

<1>

37 (50)

2A0143

143

<1>

45 (60)

2A0169

169

<1>

55 (75)

2A0211

211

<1>

75 (100)

2A0273

273

<1>

90 (125)

2A0343

343

<2>

110 (150)

2A0396

396

<2>

<1> Assumes the carrier frequency is set to 5 kHz.
<2> Assumes the carrier frequency is set to 2 kHz.

Motor Capacity kW (HP)

Three-Phase 400 V Class

Input Voltage < 460 V

Input Voltage ≥ 460 V

Model CIMR-Zo

Rated Output Current (A)

1.5 (2)

2.2 (3)

4A0005

4.8

<1>

3.0 (4)

3.7 (5)

4A0008

7.6

<1>

4.0 (5)

5.5 (7.5)

4A0011

11

<1>

5.5 (7.5)

7.5 (10)

4A0014

14

<1>

7.5 (10)

11 (15)

4A0021

21

<1>

11 (15)

15 (20)

4A0027

27

<1>

15 (20)

18.5 (25)

4A0034

34

<1>

18.5 (25)

22 (30)

4A0040

40

<1>

22 (30)

30 (40)

4A0052

52

<1>

30 (40)

37 (50)

4A0065

65

<1>

37 (50)

45 (60)

4A0077

77

<1>

45 (60)

55 (75)

4A0096

96

<1>

55 (75)

75 (100)

4A0124

124

<1>

75 (100)

90 (125)

4A0156

156

<1>

90 (125)

110 (150)

4A0180

180

<1>

110 (150)

150 (200)

4A0240

240

<2>

160 (220)

185 (250)

4A0302

302

<2>

1.2 General Description

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual

25

1