Factory recommended branch circuit protection, D.3 ul/cul standards – Yaskawa AC Drive Z1000 User Manual

Page 369

Advertising
background image

Wire Gauge

Terminal

Screws

Crimp Terminal

Model Number

Tool

Insulation

Cap

Model No.

Code

<1>

Machine No.

Die Jaw

8 mm

2

8 AWG

M4

8-4NS

YA-4

AD-901

TP-008

100-064-249

M5

R8-5

YA-4

AD-901

TP-008

100-054-032

14 mm

2

6 AWG

M5

R14-5

YA-4

AD-902

TP-014

100-054-034

M8

R14-8

YA-5

AD-952

TP-014

100-054-035

22 mm

2

4 AWG

M5

22-5NS

YA-5

AD-953

TP-022

100-051-262

M8

R22-8

YA-5

AD-953

TP-022

100-051-263

30 / 38 mm

2

3 / 2 AWG

M8

R38-8

YA-5

AD-954

TP-038

100-051-264

50 / 60 mm

2

1 AWG

1/0 AWG

1/0 AWG × 2P

M8

R60-8

YA-5

AD-955

TP-060

100-051-265

70 mm

2

2/0 AWG

2/0 AWG × 2P

M8

CB70-S8

YF-1 YET-300-1

TD-322,TD-311

TP-080

100-064-417

70-8

100-064-250

M10

70-10

YF-1 YET-300-1

TD-322,TD-311

TP-080

100-064-251

80 mm

2

3/0 AWG × 2P

3/0 AWG × 4P

M10

80-10

YF-1 YET-300-1

TD-323,TD-312

TP-080

100-051-267

M12

80-L12

YF-1 YET-300-1

TD-323,TD-312

TP-080

100-051-558

100 mm

2

4/0 AWG × 2P

4/0 AWG × 4P

M12

100-L12

YF-1 YET-300-1

TD-324,TD-312

TP-100

100-051-560

150 mm

2

250 kcmil × 2P

300 kcmil × 2P

M12

150-L12

YF-1 YET-300-1

TD-325,TD-313

TP-150

100-051-562

<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection.

Example 1: Models with 300 kcmil for both input and output require one set for input terminals and one set for output terminals, so the user should
order two sets of [100-051-272].
Example 2: Models with 4/0 AWG × 2P for both input and output require two sets for input terminals and two sets for output terminals, so the user
should order four sets of [100-051-560].

Note:

Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum allowable

temperature of 75 °C 600 Vac UL-approved vinyl-sheathed insulation.

n

Factory Recommended Branch Circuit Protection

WARNING! Fire Hazard. Install adequate branch circuit protection according to applicable local codes and this manual. Failure to comply

could result in fire and damage to the drive or injury to personnel. The device is suitable for use on a circuit capable of delivering not more

than 100,000 RMS symmetrical amperes, 240 Vac (200 V class) and 480 Vac (400 V class), when protected by branch circuit protection

devices specified in this manual.

Branch circuit protection shall be provided by any of the following: Non-time delay Class J, T, or CC fuses sized at 300% of the drive input

rating, or Time delay Class J, T, or CC fuses sized at 175% of the drive input rating, or MCCB sized at 200% maximum of the drive input

rating.

Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with UL508C.

Semiconductor protective type fuses are preferred. Alternate branch circuit protection devices are also listed in

Table 6.3

.

Table D.4 Factory Recommended Z1000 AC Drive Branch Circuit Protection

Model

Nominal Output

Power (HP)

AC Drive Input

(A)

MCCB Rating (A)

<1>

Time Delay Fuse

Rating (A)

<2>

Non-time Delay

Fuse Rating (A)

<3>

Bussmann

Semiconductor

Fuse Model

(Fuse Ampere)

<4>

Three-Phase 200 V Class

2A0011

3

10.6

20

17.5

30

FWH-40B (40)

2A0017

5

16.7

30

25

50

FWH-50B (50)

2A0024

7.5

24.2

40

40

70

FWH-80B (80)

2A0031

10

30.8

60

50

90

FWH-100B (100)

2A0046

15

46.2

90

80

125

FWH-150B (150)

2A0059

20

59.4

110

100

175

FWH-175B (175)

2A0075

25

74.8

150

125

200

FWH-225A (225)

D.3 UL/cUL Standards

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual

369

D