H3-01: terminal a1 signal level selection, Setting 1: 0 to 10 v without zero limit, Setting 2: 4 to 20 ma current input – Yaskawa AC Drive Z1000 User Manual

Page 174

Advertising
background image

Predefined V/f Patterns for Models 2A0211 to 2A0396 and 4A0124 to 4A0590

The values in the following graphs are specific to 200 V class drives. Double the values for 400 V class drives.

Table 4.34 Rated Torque Characteristics, Settings 0 to 3

Setting = 0

50 Hz

Setting = 1

60 Hz

Setting = 2

60 Hz

Setting = 3

72 Hz

0

6.9

230

1.3 2.5

50

13.8

V

oltage (V)

Frequency (Hz)

0

6.9

230

1.5 3

60

13.8

V

oltage (V)

Frequency (Hz)

0

6.9

13.8

230

1.5 3

60

50

V

oltage (V)

Frequency (Hz)

0

6.9

13.8

230

1.5 3

72

60

V

oltage (V)

Frequency (Hz)

Table 4.35 Variable Torque Characteristics, Settings 4 to 7

Setting = 4

50 Hz

Setting = 5

50 Hz

Setting = 6

60 Hz

Setting = 7

60 Hz

0

5.8

230

1.3

25

50

40.3

V

oltage (V)

Frequency (Hz)

0

6.9

230

1.3

25

50

57.5

V

oltage (V)

Frequency (Hz)

0

5.8

230

1.5

30

60

40.3

V

oltage (V)

Frequency (Hz)

0

6.9

230

1.5

30

60

57.5

V

oltage (V)

Frequency (Hz)

Table 4.36 High Starting Torque, Settings 8 to B

Setting = 8

50 Hz

Setting = 9

50 Hz

Setting = A

60 Hz

Setting = B

60 Hz

0

8.1

230

1.3 2.5

50

17.3

V

oltage (V)

Frequency (Hz)

0

10.4

230

1.3 2.5

50

23

V

oltage (V)

Frequency (Hz)

0

8.1

230

1.5 3

60

17.3

V

oltage (V)

Frequency (Hz)

0

12.7

230

1.5 3

60

23

V

oltage (V)

Frequency (Hz)

Table 4.37 Constant Output, Settings C to F

Setting = C

90 Hz

Setting = D

120 Hz

Setting = E

180 Hz

Setting = F

60 Hz

0

6.9

13.8

230

1.5 3

90

60

V

oltage (V)

Frequency (Hz)

0

6.9

13.8

230

1.5 3

120

60

V

oltage (V)

Frequency (Hz)

0

6.9

13.8

230

1.5 3

180

60

V

oltage (V)

Frequency (Hz)

0

6.9

230

1.5 30

60

57.5

V

oltage (V)

Frequency (Hz)

n

H3-01: Terminal A1 Signal Level Selection

Selects the input signal level for analog input A1. Set jumper S1 on the terminal board accordingly for voltage input or current

input.

No.

Name

Setting Range

Default

H3-01

Terminal A1 Signal Level Selection

0 to 3

0

Setting 0: 0 to 10 V with Zero Limit

The input level is 0 to 10 Vdc with zero limit. The minimum input level is limited to 0%, so that a negative input signal due

to gain and bias settings will be read as 0%.

Setting 1: 0 to 10 V without Zero Limit

The input level is 0 to 10 Vdc without zero limit. If the resulting voltage is negative after being adjusted by gain and bias

settings, then the motor will rotate in reverse.

Setting 2: 4 to 20 mA Current Input

The input level is 4 to 20 mA. Negative input values by negative bias or gain settings are limited to 0%.