A

B

B

C

A – SW1 (ON)
B – Screw (OFF)

C – SW2 (ON)

Figure 3.37 EMC Filter Switch Location (4A0302)

If the SW1/SW2 screws are missing, install proper size screws with the proper tightening torque as shown in

Table 3.6

.

NOTICE: Do not use screws of different sizes in SW1 and SW2. Failure to comply may cause overheating.

Table 3.6 SW1/SW2 Screw Sizes and Tightening Torques

Drive Model

SW1/SW2 Screw Size

Tightening Torque

2A0011

2A0017

4A0005

4A0008

4A0011

M3 × 16

0.5 to 0.6 N

•m

2A0024

2A0031

4A0014

4A0021

4A0027

M3 × 16

0.5 to 0.6 N

•m

2A0046

2A0059

4A0034

4A0040

4A0052ooB

M3 × 16

0.5 to 0.6 N

•m

2A0075

2A0088

2A0114

4A0052ooA

4A0065

4A0077

4A0096

M5 × 30

2 to 2.5 N

•m

4A0124

M5 × 25

2 to 2.5 N

•m

2A0143

2A0169

2A0211

2A0273

4A0156

4A0180

4A0240

M5 × 25

2 to 2.5 N

•m

4A0302

M5 × 25

2 to 2.5 N

•m

n

Wiring the Main Circuit Terminal

WARNING! Electrical Shock Hazard. Shut off the power supply to the drive before wiring the main circuit terminals. Failure to comply may

result in death or serious injury.

Wire the main circuit terminals after the terminal board has been properly grounded.
Models 2A0011 to 2A0273 and 4A0005 to 4A0302 have a cover placed over the 12/18 rectification terminals prior to shipment

to help prevent miswiring. Use wire cutters to cut away covers as needed for terminals.
Refer to

Figure 3.4

on page

65

for details.

n

Main Circuit Connection Diagram

Refer to Main Circuit Connection Diagram on page 65

when wiring terminals on the main power circuit of the drive.

3.8 Main Circuit Wiring

90

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual