Low voltage wiring for control circuit terminals – Yaskawa AC Drive Z1000 User Manual

Page 370

Advertising
background image

Model

Nominal Output

Power (HP)

AC Drive Input

(A)

MCCB Rating (A)

<1>

Time Delay Fuse

Rating (A)

<2>

Non-time Delay

Fuse Rating (A)

<3>

Bussmann

Semiconductor

Fuse Model

(Fuse Ampere)

<4>

2A0088

30

88

175

150

250

FWH-225A (225)

2A0114

40

114

225

175

300

FWH-250A (250)

2A0143

50

143

250

250

400

FWH-275A (275)

2A0169

60

169

300

275

500

FWH-350A (350)

2A0211

75

211

400

350

600

FWH-400A (400)

2A0273

10

273

500

450

<5>

FWH-450A (450)

2A0343

125

343

600

600

FWH-600A (600)

2A0396

150

396

700

<5>

FWH-600A (600)

Three-Phase 400 V Class

4A0005

3

4.8

15

8

12

FWH-40B (40)

4A0008

5

7.6

15

12

20

FWH-40B (40)

4A0011

7.5

11

20

17.5

30

FWH-45B (45)

4A0014

10

14

25

20

40

FWH-45B (45)

4A0021

15

21

40

35

60

FWH-60B (60)

4A0027

20

27

50

45

80

FWH-60B (60)

4A0034

25

34

60

50

100

FWH-125B(125)

4A0040

30

40

75

70

110

FWH-150B (150)

4A0052

40

52

100

90

150

FWH-200B (200)

4A0065

50

65

125

110

175

FWH-225A (225)

4A0077

60

77

150

125

225

FWH-225A (225)

4A0096

75

96

175

150

275

FWH-225A (225)

4A0124

100

124

225

200

350

FWH-250A(250)

4A0156

125

156

300

250

450

FWH-300A (300)

4A0180

150

180

350

300

500

FWH-350A (350)

4A0240

200

240

450

400

<5>

FWH-400A (400)

4A0302

250

302

600

500

FWH-600A (600)

4A0361

300

346

600

600

1000

<6>

FWH-800A (800)

4A0414

350

410

800

700

1200

<6>

FWH-800A (800)

4A0480

400

480

900

<5>

<5>

FWH-700A (700)

4A0590

500

590

1100

FWH-1000A

(1000)

<1> Maximum MCCB rating is 15 A, or 200% of drive input current rating, whichever value is larger. MCCB voltage rating must be 600 Vac or greater.
<2> Maximum Time delay fuse is 175% or drive input current rating. This covers any Class J, T, or CC fuse.
<3> Maximum Non-time delay fuse is 300% of drive input current rating. This covers any Class J, T, or CC fuse.
<4> When using semiconductor fuses, Bussmann FWH fuses are required for UL compliance.
<5> Consult factory.
<6> Class L fuse is also approved for this rating.

n

Low Voltage Wiring for Control Circuit Terminals

Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. The external

power supply shall be a UL listed Class 2 power supply source or equivalent only. Refer to NEC Article 725 Class 1, Class

2, and Class 3 Remote-Control, Signaling, and Power Limited Circuits for requirements concerning class 1 circuit conductors

and class 2 power supplies.

Table D.5 Control Circuit Terminal Power Supply

Input / Output

Terminal Signal

Power Supply Specifications

Multi-function digital inputs

S1, S2, S3, S4, S5, S6, S7, SC, SP, SN

Use the internal control power supply of the drive or an

external class 2 power supply.

Multi-function analog inputs

+V, A1, A2, AC, FM, AM

D.3 UL/cUL Standards