Yaskawa AC Drive Z1000 User Manual

Page 160

Advertising
background image

n

b3-10: Speed Search Detection Compensation Gain

Sets the gain for the detected motor speed of the Speed Estimation Speed Search. Increase the setting only if an overvoltage

fault occurs when the drive restarts the motor.

No.

Name

Setting Range

Default

b3-10

Speed Search Detection Compensation Gain

1.00 to 1.20

1.05

n

b3-14: Bi-Directional Speed Search Selection

Sets how the drive determines the motor rotation direction when performing Speed Estimation Speed Search.

No.

Parameter Name

Setting Range

Default

b3-14

Bi-Directional Speed Search Selection

0, 1

1

Setting 0: Disabled

The drive uses the frequency reference to determine the direction of motor rotation to restart the motor.

Setting 1: Enabled

The drive detects the motor rotation direction to restart the motor.

n

b3-17: Speed Search Restart Current Level

Sets the current level at which Speed Estimation is restarted as a percentage of drive rated current to avoid overcurrent and

overvoltage problems since a large current can flow into the drive if the difference between the estimated frequency and the

actual motor speed is too big when performing Speed Estimation.

No.

Name

Setting Range

Default

b3-17

Speed Search Restart Current Level

0 to 200%

110%

n

b3-18: Speed Search Restart Detection Time

Sets the time for which the current must be above the level set in b3-17 before restarting Speed Search.

No.

Name

Setting Range

Default

b3-18

Speed Search Restart Detection Time

0.00 to 1.00 s

0.10 s

n

b3-19: Number of Speed Search Restarts

Sets the number of times the drive should attempt to find the speed and restart the motor. If the number of restart attempts

exceeds the value set to b3-19, the SEr fault will occur and the drive will stop.

No.

Name

Setting Range

Default

b3-19

Number of Speed Search Restarts

0 to 10

3

n

b3-24: Speed Search Method Selection

Sets the Speed Search method.

No.

Parameter Name

Setting Range

Default

b3-24

Speed Search Method Selection

0, 1

0

Setting 0: Current Detection
Setting 1: Speed Estimation

n

b3-25: Speed Search Wait Time

Sets the wait time between Speed Search restarts. Increase the wait time if problems occur with overcurrent, overvoltage, or

if the SEr fault occurs.

No.

Name

Setting Range

Default

b3-25

Speed Search Wait Time

0.0 to 300.0 s

0.5 s

4.13 Advanced Drive Setup Adjustments

160

YASKAWA ELECTRIC TOEP C710616 45E YASKAWA AC Drive – Z1000 User Manual

Advertising