Changing the switch’s temperature threshold – Allied Telesis AT-S63 User Manual

Page 74

Advertising
background image

Chapter 3: Basic Switch Parameters

74

Section I: Basic Features

The System Hardware Information menu provides the following
information:

System 1.25 V Power
System 1.8V Power
System 2.5 V Power
System 3.3 V Power
System 5 V Power
System 12 V Power
The current voltage of the six power supplies in the switch.

System Temperature (Celsius)
The overall system temperature.

System Fan Speed
The system fan speed.

Main PSU
RPS
The status of the main power supply unit (PSU) and the redundant
power supply (RPS).

Changing the

Switch’s

Temperature

Threshold

You can set a temperature threshold on the switch which, if exceeded,
causes the unit to send an SNMP trap to your management station. The
default is 73

°

Celsius.

To change the temperature threshold for the switch, perform the
following procedure:

1. From the Main Menu, type 5 to select System Administration.

The System Administration menu is shown in Figure 4 on page 51.

2. From the System Administration menu, type 2 to select System

Configuration.

The System Configuration menu is shown in Figure 5 on page 52.

3. From the System Configuration menu, type 9 to select Configure

System Hardware.