Chapter 7

Power Connections

Chapter 7

DC bus, single phase AC power and motor connections are provided
on the Terminal Block (TB-1).

Power Wiring Connection Diagrams for the 1398-DDM-005 and
-005X, 1398-DDM-009 and -009X, 1398-DDM-019 and -019X are
provided in Figure 5.4 on page 5-11. Wiring for the external I/O
power is described and depicted in the chapter “Application and
Configuration Examples” on page 8-1.

Table 7.1:

TB1 - DC Bus and AC Power Terminal Block Connections

Description

Identifier

Terminal

1398-DDM-005 and -005X
1398-DDM-009 and -009X
1398-DDM-019 and -019X

DC Bus + voltage

DC BUS +

1

DC Bus - voltage

DC BUS -

2

100-240 VAC input power L1 (Line 1)

3

100-240 VAC input power L2 (Line 2)/

N (Neutral)

4

Safety (earth) ground

5

R phase power to motor

R

6

S phase power to motor

S

7

T phase power to motor

T

8

Motor case ground

9

!

Intro

ATTENTION: DC bus capacitors may retain hazardous
voltages after input power has been removed, but will nor-
mally discharge in several seconds. Before working on the
drive, measure the DC bus voltage to verify it has reached
a safe level or wait the full time interval listed on the warn-
ing on the front of the drive. Failure to observe this
precaution could result in severe bodily injury or loss of
life.

!

Intro

ATTENTION: Motor power connectors are for assembly
purposes only. They should not be connected or discon-
nected while the drive is powered.