Cable Diagrams, Schematics and Examples

B-27

Figure B.27

Y-Series Motors to ULTRA 100 Series Drive
using P2 Terminal Strip

Intro

Table B.1:

9/260 or 9/290 to Breakout Board

9/260 or 9/290 8520-

ASM-3

Breakout Board Connections via J2

1398-DDM-005, -005X, -009, -009X, -019 or -019X

J1, J2, J3

Pin

Signal

J2

Pin

Signal

3

CHA_HI

7

MtrEncdr Input Chnl A+

4

CHB_HI

9

MtrEncdr Input Chnl B+

9101-1385-XXX

Clamp exposed

to the chassis

Motor

P2

ground terminal

motor cable shield

Screw Terminal Strip

Enclosure/Cabinet

P1

9101-1391

To

Control

Interface

9101-1392

Screw Terminal Strip

Motor Power connectors

Encoder Connectors

9101-1373-XXX

Pigtail cable to

machine chassis

CPC connectors

NOTES:

This wiring method provides the option to run cables through a restrictive bulkhead or enclosure.

Cable 9101-1373-XXX has a connector on the motor end only. The cable connector is molded
and potted to the cable and may not be disassembled. Refer to the schematic for cable 9101-
1375-XXX for information on wiring this cable to the J2 Terminal Strip.

Adaptor Kit 9101-1391 includes the 3 foot cable, screw terminal strip and mounting bracket. The
cable has a 50-pin Mini D ribbon connector at the drive end and a 50-pin D connector at the ter-
minal strip end.

Adaptor Kit 9101-1392 includes the 3 foot cable, screw terminal strip and mounting bracket. The
cable has a 20-pin Mini D Ribbon connector at the drive end and a 20-pin D connector at the ter-
minal strip end.

LD-Series Motors have 1 meter (39 inch) cables attached.

ground