Publication 1398-5.2 – PDF 1997

Application and Configuration Examples

8-39

• Status LED is green. Refer to “Status Indicator” on page 10-1

for an explanation of the display codes.

2. Start ULTRA Master on the PC.

3. Choose

Cancel

from the Drive Select dialog box.

4. Select

P

C Set Up

from the Communications menu in

ULTRA Master to display the personal computer’s communica-
tion settings.

5. Verify the communications port settings of the PC match those of

the drive.

• If the settings are correct, select

OK

in the Port - Settings dia-

log box.

• If the settings are different, correct the Port - Settings to allow

communications with the drive.

Factory default communications Port - Settings for the drive
are:

– Baud Rate:

9600

– Data Bits:

8

– Parity:

None

– Stop Bits:

1

– Serial Port:

COM1

Refer to “RS-232 Communication Test” on page 11-8 for
troubleshooting instructions.

6. Select

Read Drive

P

arameters

from the Communications menu.

7. Verify the Drive Name and Address are correct for the drive that is

being addressed.

8. Choose

OK

to load the drive parameters.

9. If the message box appears that a motor must be selected, select

OK. The Drive Setup window is displayed with Motor Model
selection parameter active. The motor may be selected from the
drop down box. If this message box does not appear, the motor
displayed in the Motor Model box was previously selected.

10. Select or verify the correct motor model number from the drop

down Motor Model list.

11. If a message advises that the drive must be reset, choose

Yes

.

12. Select

Inde

x

ing

as the Operation Mode for the drive.

Note: A motor must be selected for the parameters to load.