Incremental indexing connection diagram, Data bits, Parity – Rockwell Automation 1398-DDM-xxx ULTRA 100 Series Drives Installation Manual User Manual

Page 146: Stop bits, Serial port

Advertising
background image

Publication 1398-5.2 – PDF 1997

8-32

Application and Configuration Examples

5. Verify the communications port settings of the PC match those of

the drive.

• If the settings are correct, select

OK

in the Port - Settings dia-

log box.

• If the settings are different, correct the Port - Settings to allow

communications with the drive.

Factory default communications Port - Settings for the drive
are:

– Baud Rate:

9600

– Data Bits:

8

– Parity:

None

– Stop Bits:

1

– Serial Port:

COM1

Refer to the section “RS-232 Communication Test” on page 11-8
for troubleshooting instructions.

6. Select

Read Drive

P

arameters

from the Communications menu.

7. Verify the Drive Name and Address are correct for the drive that is

being addressed.

8. Choose

OK

to load the drive parameters.

Figure 8.7

Incremental Indexing Connection Diagram

J1

26 I/O PWR

20 ENABLE

21 FAULT

32 INPUT1

Close to ENABLE Drive

Close to RESET Fault

J4

DRIVE

TB1

2 RCV

3 XMT

5 COM

L1 3

L2/N 4

Gnd 5

XMT

RCV

COM

100-240 VAC

50/60 Hz

Single Phase

Power Source

TB1

Phase R 6

Phase S 7

Phase T 8

Motor Gnd 9

J2

Motor
Encoder

RESET

Close to Start INDEX

External I/O

12-24 VDC

Power Source

5 I/O PWR

6 I/O COM

Note: A motor must be selected for the parameters to load.