Connection diagram, Configuration, Registration indexing connection diagram – Rockwell Automation 1398-DDM-xxx ULTRA 100 Series Drives Installation Manual User Manual

Page 152: E figure 8.9, Connection diagram configuration

Advertising
background image

Publication 1398-5.2 – PDF 1997

8-38

Application and Configuration Examples

4. Connect the Index Sensor to the drive as shown in the diagram.

5. Connect a jumper wire with a toggle switch between the following

pins:

• J1-20 (ENABLE) and J1-26 (I/O PWR)

• J1-32 (INPUT1) and J1-26 (I/O PWR)

• J1-33 (INPUT2) and J1-26 (I/O PWR)

• J1-21 (FAULT RESET) and J1-26 (I/O PWR).

These connections provide manual control for enabling or
disabling the drive and resetting faults. The figure below shows
the jumper, including normally open toggle switches.

6. Connect an external 12 to 24 VDC power source for powering I/O

to J1-5 (I/O PWR) and J1-6 (I/O COM).

7. Connect the drive to a single phase 100-240 VAC, 50/60 Hz power

source.

Connection Diagram

Configuration

Carefully check all connections before entering these parameters.

1. Switch the AC Power to ON and verify:

Figure 8.9

Registration Indexing Connection Diagram

J1

26 I/O PWR

20 ENABLE

21 FAULT

32 INPUT1

Close to ENABLE Drive

Close to RESET Fault

J4

DRIVE

TB1

2 RCV

3 XMT

5 COM

L1 3

L2/N 4

Gnd 5

XMT

RCV

COM

100-240 VAC

50/50 Hz

Single Phase

Power Source

TB1

Phase R 6

Phase S 7

Phase T 8

Motor Gnd 9

J2

Motor
Encoder

RESET

Close to Start INDEX

Close for Registration
Sensor

33 INPUT2

External I/O

12-24 VDC

Power Source

5 I/O PWR

6 I/O COM