Publication 1398-5.2 – PDF 1997

5-2

Installation

• Altitude: 1500 meters (5000 feet),

Derate power performance 3% for each 300 m above 1500 m
(1000 ft above 5000 ft).

• Humidity: 5% to 95% non-condensing

Ambient operating temperature range and airflow clearances are:

• 0

°

to 55

°

Celsius (32

°

to 131

°

Fahrenheit).

• 50.8 mm (2 inches) above and below unit for airflow.

4. Bolt the unit to the cabinet using the mounting slots in the drive.

Mounting dimensions are shown in Figure 5.2. The recommended
size of mounting hardware is:

• M5 Metric (1/4-20 equivalent), or

• #10 MS bolts