Testing analog input – Rockwell Automation 1398-DDM-xxx ULTRA 100 Series Drives Installation Manual User Manual

Page 194

Advertising
background image

Publication 1398-5.2 – PDF 1997

11-12

Maintenance and Troubleshooting

4. From the Output Diagnostics window select

Analog Output 1

.

5. Enter 1000 in the D/A level box.

6. Connect a DC voltmeter across analog test points J1-31 and J1-28.

The meter should read approximately 1 Vdc.

7. Repeat step using different positive or negative values for the D/A

Level. Verify the meter reads the values you enter.

If you determine that the output is defective, please refer to “Return
Procedure” on page Help-7
to return the unit.

Testing Analog Input

The following test verifies the functionality of the analog input.

The tests require:

a PC running ULTRA Master, and

a 10 kOhm potentiometer.

Testing the Current Limit Input

1. Verify the accuracy of the potentiometer with an ohmmeter before

installing.

2. Disable the drive by opening the connections between the

ENABLE input and the I/O Power (I/O PWR).

3. Disconnect the connections to J1-27 and J1-28.

4. Connect the 10K potentiometer between J1-27 and J1-28.

Refer to “J1 – Controller” on page 6-1 for a diagram showing the
location of the pins.

5. Choose the

Drive

S

ignals

command icon from ULTRA Master.

6. Choose

S

et Up

, if the Drive Signals Set Up window is not already

active.

7. Choose

Current - Input Limit +

as the analog signal.

8. Choose

OK

to close the Set Up window and activate the Drive

Signals window.

9. Slowly adjust the potentiometer while viewing the Drive Signals

window. The Current - Input Limit + value should update as the
potentiometer is adjusted.

If you determine that the analog input is defective, refer to “Return
Procedure” on page Help-7
to return the unit.

Note: This test assumes that I/O power is 24 VDC.

Advertising