Testing encoder inputs – Rockwell Automation 1398-DDM-xxx ULTRA 100 Series Drives Installation Manual User Manual

Page 195

Advertising
background image

Publication 1398-5.2 – PDF 1997

Maintenance and Troubleshooting

11-13

Testing Encoder Inputs

The following test verifies both reception and transmission of the line
count from an encoder by the drive.

The tests require:

a PC running ULTRA Master, and

a motor encoder.

Testing Encoder Inputs

1. Disable the drive by opening the connections between the

ENABLE input and I/O Power (I/O PWR).

2. Choose the

D

rive Set Up

command icon from ULTRA Master.

3. Choose

Divide by 1

as the Motor Encoder Output Signal.

4. Make the following hardware connections:

• Connect the motor encoder to J2.

• Jumper the Auxiliary Encoder Inputs to the Motor Encoder

Outputs by connecting the following pins:

5. Choose the

E

ncoder Diagnostics

command icon from

ULTRA Master.

6. Choose

Z

ero Count

for both the Motor Encoder and Master Posi-

tion Input.

7. Slowly rotate the encoder shaft by hand while observing the

counts for both the Motor Encoder and Master Position Input. The
Motor Encoder and Master Position Input line counts should be
equal.

If you determine that the analog input is defective, refer to “Return
Procedure” on page Help-7
to return the unit.

Note: This test assumes that I/O power is 24 VDC.

J1-7 to J1-14

J1-10 to J1-17

J1-8 to J1-15

J1-11 to J1-18

J1-9 to J1-16

J1-12 to J1-19