Tuning, Operation – Rockwell Automation 1398-DDM-xxx ULTRA 100 Series Drives Installation Manual User Manual

Page 155

Advertising
background image

Publication 1398-5.2 – PDF 1997

Application and Configuration Examples

8-41

Tuning

1. Choose the

Tuning

command icon from the Drive window.

2. Select

A

utoTune

from the Tuning mode group.

3. Select the appropriate values for the following Auto Tune com-

mands:

Distan

c

e

and

S

t

ep Current

.

4. Select the appropriate entry for the Motor Direction:

• B

iDirectional

,

For

w

ard Only

or

R

e

verse Only

.

5. Close the toggle switch between J1-26 and J1-20 to enable the

drive.

6. Choose

S

tart

from the Tuning window. The drive powers the

motor shaft for a short period and then motion will cease. Then
ULTRA Master displays the calculated gains and disables the
drive.

7. Choose

N

ormal Drive Operation

from the Tuning window.

8. Open the switch between J1-26 and J1-20 to disable the drive.

9. Choose

C

lose

to exit the Tuning window.

10. Verify the Status indicator is green.

11. Close any open windows or dialog boxes.

Operation

The drive is now configured as a Registration Indexing controller.

The servo parameters have been setup with the unloaded motor.

Motion is commanded through the inputs.

Note: Do not attempt to Auto Tune systems that have gravitational
effects. The ULTRA 100 Series will not hold initial position.

!

Intro

ATTENTION: Rotating motor shafts can cause extensive
damage and injury. Motors must be properly guarded dur-
ing testing and installation.

Advertising