Specifications

G-5

Power

Power Dissipation

ULTRA 100 Series drives dissipate power that results in cabinet
heating. The following table lists power dissipation values. Calculate
the cabinet cooling requirements using the power dissipation
information and formulas below.

Maximum power losses are shown to help size a NEMA 12 or
equivalent enclosure and to ensure the required ventilation. Typical
power losses are about one-half maximum power losses.

When sizing an enclosure with no active method of heat dissipation,
the following equation approximates the size of enclosure necessary:

1398-DDM-005 &
1398-DDM-005X

1398-DDM-009 &
1398-DDM-009X

1398-DDM-019 &
1398-DDM-019X

AC Input
Voltage and Frequency

100-240 Vac

rms

nominal
Single Phase

47 - 63 Hz

100-240 Vac

rms

nominal
Single Phase

47 - 63 Hz

100-240 Vac

rms

nominal
Single Phase

47 - 63 Hz

AC Input Current

5 A

rms

9 A

rms

18 A

rms

Bus Voltage

141-339 Vdc

141-339 Vdc

141-339 Vdc

Output Peak Current

7.5 Amps

15 Amps

30 Amps

Continuous Output
Current (peak)

2.5 Amps

5 Amps

10 Amps

Bus Capacitance Energy
Absorption
(from 325-400 Vdc Bus)

a

38 Joules
C=1410uF

51 Joules
C=1880uF

51 Joules
C=1880uF

Peak Power Output

b

120 Vac 0.9 kWatts
240 Vac1.8 kWatts

120 Vac 1.3 kWatts
240 Vac 2.7 kWatts

120 Vac 2.7 kWatts
240 Vac 5.5 kWatts

Continuous Power Output

b

120 Vac 0.3 kWatts
240 Vac 0.6 kWatts

120 Vac 0.6 kWatts
240 Vac 1.2 kWatts

120 Vac 1.2 kWatts
240 Vac 2.5 kWatts

a. Bus capacitance energy absorption is based on the following equations:

b. Power outputs are based on the following equation:

ε

1
2

--- C V

2

f

(

)

1
2

---C V

2

i

(

)

=

ε

1
2

--- C 420

(

)

2

1
2

--- C 325

(

)

2

=

1
2

--- C

420

2

325

2

(

)

C 35387

(

)

=

ifC

17

470uF

×

E

282

=

,

=

kWatts

VAC

I

R ma x

2

--------------

Ч

3

Ч

0.85

Ч

=

Current as % of Rated Con-

tinuous Current

1398-DDM-005 &

1398-DDM-005X

1398-DDM-009 &

1398-DDM-009X

1398-DDM-019 &

1398-DDM-019X

100

48 W

48 W

50 W

NOTE: These values do

not include external shunt regulator power (regenerated power).