Selectable output circuits, Output1 and output2 functions – Rockwell Automation 1398-DDM-xxx ULTRA 100 Series Drives Installation Manual User Manual

Page 75

Advertising
background image

Publication 1398-5.2 – PDF 1997

Interfaces

6-11

The current limiting input supports 0 to +10 Volt signals

Table 6.8:

Selectable Output Circuits

Digital Out-

put

Pin Number

Function/Description

READY

J1-24 (+)
J1-25 (-)

Relay closure indicates the drive is operational and does

not have

a fault.

Refer to “READY and BRAKE/DRIVE ENABLED Output Specifi-
cations” on page 6-9

BRAKE

J1-49 (+)
J1-50 (-)

Relay closure releases the brake. Delay time is selectable (Refer
to ULTRA Master - I/O configuration) and may be used as a drive
enabled output.
This signal is the inverse of the ENABLE output, although a time
delay may be selected.

Refer to “READY and BRAKE/DRIVE ENABLED Output Specifi-
cations” on page 6-9

OUTPUT 1

J1-42

General purpose output. Selectable from one of several drive
functions.
(Refer to ULTRA Master - I/O configuration on-line Help and
Table 6.9.)

OUTPUT 2

J1-43

General purpose output. Selectable from one of several drive
functions.
(Refer to ULTRA Master - I/O configuration on-line Help and
Table 6.9.)

Table 6.9:

OUTPUT1 and OUTPUT2 Functions

Function

Description

In Position

An active state indicates the position window condition is satisfied, and
the zero speed condition is satisfied. The position window and zero speed
range are selectable settings.

Within Window

An active state indicates the position window condition is satisfied. The
position window range is a selectable setting.

Zero Speed

An active state indicates the velocity loop zero speed signal is active. The
zero speed limit is a selectable setting.

Speed Window

An active state indicates the velocity loop speed window is active. The
speed window range is a selectable setting.

Current Limit

An active state indicates the torque current is limited.

Up To Speed

An active state indicates the velocity loop AT SPEED signal is active. The
at speed level is a selectable setting.

Drive Enabled

An active state indicates the ENABLE signal is active and no fault is
detected.

Bus Charged

An active state indicates the DC bus is energized.

Disabling Fault

An active state indicates a fault disabled the drive.

In Motion

An active state indicates the indexing sequence is in the motion portion.

In Dwell

An active state indicates the indexing sequence is in the dwell portion.

Sequence Complete

An active state indicates all batches of the indexing sequence are fin-
ished.

Registered

An active state indicates the indexing move has been adjusted after sens-
ing the registration sensor.

At Home

An active state indicates the drive is at the home position.

Axis Homed

An active state indicates the drive has been homed.

NOTE: Refer to the I/O Configuration section of the ULTRA Master on-line Help for further expla-
nation of these output signals.