Unpacking, Inspecting and Storing

2-7

Initial Drive Operation

1. When the message appears that a motor must be selected, choose

OK

. The Drive Set Up dialog box is selected with Motor Model

active.

2. Select the appropriate motor from the drop-down Motor Model

box.

3. Choose

OK

when the message appears advising that the drive

must reset. A change in motor parameters requires reselection of
the firmware based drive/motor tables. The software reset pre-
vents improper sequencing of these table parameters.

4. Choose

Close

from the Drive Set Up window.

5. Select the

Control

P

anel

icon from the Drive Window.

6. Close the connection between J1-26 and J1-20 to enable the drive.

7. Holding torque should be sufficient so that the shaft is either

immovable or very resistant to rotation.

8. Move the Slide Bar in the Control Panel window to the right and

then to the left. Verify that the motor rotates:

• CW as the Slide Bar is moved right of center, and

• CCW as the Slide Bar is moved left of center.

If the motor rotates in the wrong direction (CCW when the slide
bar is set to the right of center) or jumps and locks-up, motor
phasing and encoder feedback phasing may be incorrect. If
necessary, refer to the Troubleshooting chapter for instructions on
how to correct the motor power connections at TB1-1, 2, 3 and 4
or the encoder feedback connections at J2.

9. Choose

Set to

Z

ero

. The motor will stop rotating.

10. Choose

Drive

D

isable

and verify the motor shaft can be rotated

by hand.

11. Choose

Drive

E

nable

and verify the motor shaft has holding

torque. (i.e., The shaft cannot be moved or moves with resistance.)

12. Open the connection between J1-26 and J1-20 to disable the drive.

13. Choose

Close

from the Control Panel window.