Fault Handling

Reload the file.

4.1.7.1.19 ModBus Offline

Fault Meaning:

The Modbus client can't communicate.

Fault Indication:

LED Indicator:

When this error is detected, the following LEDs will light up:

o

G. Fault LED on the front panel of the IDA8C/S.

Log:

Text messages display at the touch screen of the IDA8C:

"ModBus Offline"

Text messages display at the window [Machine Fault Record] in Ateis Studio:

A buzzing sound outputs to the monitoring speaker on the front panel of the IDA8C.

Fault Handling

Check the Modbus client communication. Once it's recovered, the LOG will show:

"ModBus Online."

4.1.7.1.20 AMP Rating Fault

Fault Meaning:

The IDA8 gets the reference value which is too low.

Fault Indication:

LED Indicator:

When this error is detected, the following LEDs will light up:

o

G. Fault LED on the front panel of the IDA8C/S.

Log:

Text messages display at the touch screen of the IDA8C:

"AMP Rating Fault"

"Zone n Normal AMP Rating too low"