Passcode and alarm – Super Systems PC Configurator 2 User Manual

Page 115

Advertising
background image

Super Systems Inc.

Page 115 of 201

Configurator Manual #4562 Rev D

PV 1 retrans

PV3 retrans

Loop 1 inc

Loop 3 inc

Loop 1 dec

Loop 3 dec

Loop 1 combo

Loop 3 combo

PV 2 retrans

Input 1 retrans

Loop 2 inc

Input 2 retrans

Loop 2 dec

Input 3 retrans

Loop 2 combo

Input 4 retrans


Combo example for carbon – 4 – 12 mA Air

12 – 20 mA Gas


Offset:
This is the starting point, the Process Variable value at which you get 4 milliamps. Clicking on
this value will display an input box from which the user can select a new value. The range is
32768
to 32767.

Range:
This is a Process Variable value between 4 and 20 milliamps. Clicking on this value will display
an input box from which the user can select a new value. The range is –32768 to 32767.

Current Selection:
Provides the option of 4-20 mA or 0-20 mA control. Clicking on this value will display an
input box with a drop-down list from which the user can select either of the two values listed
above.

Offset and Range when assigned to a control loop:
Inc -- 0 = 4mA, 100 = 20mA
Dec -- 0 = 4mA, -100 = 20mA

Example: if 4 – 20 mA = 800 mV - 1200 mV
Offset = 800 (starting point)
Range = 400

Passcode and Alarm

There are four levels of menus in the 9200 Dual loop controller - Operator, Supervisor,
Administrator, and SSi Special.