Alternate PID Setup

Configurator – Alternate PID Setup menu option


The Alternate PID Setup menu option allows for up to 16 sets of PID values to be used on all
three loops via the programmer.
This menu option is typically used for vacuum applications with the programmer.
There is a choice of PID 1 – 16, and LP1 Set 1 – LP3 Set 3.

Prop Band (0 for On/Off):
This is the proportional band for the PID setup. The range of values is –1.0 to 999.0.

Reset:
This is the reset value. The range is 0.00 through 10.00.

Rate:
This is the rate value. The range is 0.00 through 10.00.

Integral Preset:
This is the integral preset value. The range is –100 to 100.

High Limit:
This is the high limit value. The range is –100 to 100.

Low Limit:
This is the low limit value. The range is –100 to 100.