Default wait limits, Furnace name, Alarm setup – Super Systems PC Configurator 2 User Manual

Page 162

Advertising
background image

Super Systems Inc.

Page 162 of 201

Configurator Manual #4562 Rev D

Default Hold Time:
This value is the default holding time for the furnace. The range is 0 to 10000.

Clear events/end of recipe:
This switch will allow the user to clear the events out at the end of a recipe. The options are
either no or yes.

Default Wait Limits

*** This menu option is the same as the

Default Wait Limits

menu option under the

Configurator-9200 Drop Down Menu

. ***

Furnace Name

*** This menu option is the same as the

Furnace Name

menu option under the

Configurator-

9200 Drop Down Menu

. ***

Alarm Setup

Configurator – Alarm Setup menu option


The 9220 controller can be configured to use three different alarms, and a Thermocouple
Check. Each of the alarms consists of an alarm setpoint, alarm type, alarm hysteresis, smart
alarm, ON delay time, and a 0 SP blocks alarm value. The alarms come from the factory with a
default configuration dependent on the application but also can be modified prior to shipment
to your facility or in the field by a supervisor.

Setpoint:
This value is the setpoint for the alarm. Clicking on this value will display an input box from
which the user can select a new value. The range is from –9999.00 to 9999.00.

Alarm Type:
This value is the type of alarms used. Clicking on this value will display an input box with two
(2) drop-down lists from which the user can select a new value.